How to Set E.S.P?
Note: 1. The above table shows the correlation between the air rates and E.S.P.
Setting Value
70
-
-
-
-
-
-
-
-
-
80
4.0
-
-
-
-
-
-
-
-
90
12.1
6.9
4.13
-
-
-
-
-
-
100
17.0
15.5
11.01
6.2
4.2
-
-
-
-
110
21.4
19.6
17.53
14.0
11.6
6.6
-
-
-
120
25.8
24.0
21.8
19.8
17.9
14.6
12.1
-
-
130
30.0
28.5
26.93
25.3
23.4
21.8
18.1
14.6
11.3
140
36.0
32.1
30.41
29.0
27.4
25.9
21.6
17.8
14.5
143
37.5
33.9
32.1
30.7
28.8
27.2
23.0
20.1
16.8
150
41.0
38.0
36.0
34.5
32.1
30.1
26.3
22.4
18.2
160
42.4
41.6
38.2
36.1
35
34.6
31.1
26.8
23.3
5(50)
6(60)
7(70)
8(80)
9(90)
10(100)
12(120)
14(140)
16(160)
Static Pressure(mmAq(Pa))
JRNU28GBGA3, JRNU36GBGA3, JRNU42GBGA3
Setting Value
91
46.5
43.7
38.2
31.3
23.2
14.0
9.0
3.7
-
-
-
96
49.9
46.1
43.0
33.5
31.1
18.4
13.7
9.0
2.6
-
-
101
52.1
50.2
47.9
39.5
37.4
27.3
25.2
17.8
8.9
6.1
-
106
51.4
51.2
50.4
44.4
43.1
33.3
32.1
28.9
21.0
17.9
8.3
111
53.6
53.7
52.9
49.9
48.3
40.6
40.2
32.8
31.5
27.2
17.5
116
62.3
61.0
60.3
55.7
50.8
44.8
42.6
40.1
37.6
32.5
27.6
121
67.0
64.8
64.1
58.2
52.2
50.8
50.3
45.7
44.6
38.8
32.2
126
68.2
67.5
66.2
65.1
64.3
57.4
54.4
51.2
50.4
46.0
43.5
5(50)
6(60)
8(80)
10(100) 12(120) 14(140) 15(150) 16(160) 17(170) 18(180) 20(200)
Static Pressure(mmAq(Pa))
JRNU48GBRA3, JRNU54GBRA3
(Unit: CMM)
(Unit: CMM)
Note:1. The above table shows the correlation between the air rates and E.S.P.
JRNU76GB8A3, JRNU96GB8A3
Setting Value
80
76.27
69.65
55.16
-
-
-
-
-
-
-
-
85
83.26
78.59
67.4
55.88
-
-
-
-
-
-
-
91
89.7
87.09
78.87
67.55
54.18
-
-
-
-
-
-
95
93.37
91.43
86.1
77
66.4
50.58
-
-
-
-
-
100
93.4
91.35
88.26
84.9
75.85
69.54
60.76
-
-
-
-
105
93.16
91.27
88.28
84.89
81.08
77.4
69.23
67.92
51.26
-
-
111
93.47
91.42
88.42
86.07
81.44
79.16
75.92
74.96
70.72
67.3
61.4
115
93.75
91.44
88.33
86.4
81.57
80.3
75.85
75.24
72.5
68.9
63.7
6(60)
9(90)
12(120) 15(150) 18(180) 20(200) 22(220) 23(230) 25(250) 27(270) 30(300)
Static Pressure(mmAq)