13
ENGLISH
Y branch method
1 Outdoor Units
Example : 5 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch (Y branch)
Ⓒ
: Indoor Units
2 Outdoor Units
Example : 5 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch (Y branch)
Ⓒ
: Indoor Units
Ⓓ
: Downward Indoor Unit
Ⓔ
: Connection branch pipe be-
tween Outdoor units: ARCNN21
l
40m (90 m : Conditional application)
h 40m
H 110m
L150m (200 m : Conditional application)
Combination of Y
branch/header method
1 Outdoor Units
Example : 5 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch (Y branch)
Ⓒ
: Y branch
Ⓓ
: Indoor Unit
Ⓔ
: Header
Ⓕ
: Sealed piping
Header Method
1 Outdoor Unit
Example : 6 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch
Ⓒ
: Indoor Units
Ⓓ
: Sealed piping
L 200m
40m
H 110m
40m
10m or
less
L150m (200 m : Conditional application)
ODU Capacity
Master ≥ Slave1 ≥ Slave 2
l
40m (90 m : Conditional application)
H 110m
Slave
Master
h 40m
h1
2 Outdoor Units
Example : 6 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: Header branch
Ⓒ
: Indoor Units
Ⓓ
: Sealing
Ⓔ
: Connection branch pipe be-
tween Outdoor units: ARCNN21
10m or
less
L 110m
L 200m
40m
Slave
Master
Slave
Master
Slave
Master
ODU Capacity
Master ≥ Slave
40m
h1
3 Outdoor Units
Example : 6 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: Header branch
Ⓒ
: Indoor Units
Ⓓ
: Sealing
Ⓔ
: Connection branch pipe be-
tween Outdoor units: ARCNN31
Ⓕ
: Connection branch pipe be-
tween Outdoor units: ARCNN21
10m or
less
H 110m
L 200m
40m
Master
Slave2
Slave1
ODU Capacity
Master ≥ Slave1 ≥ Slave2
40m
h1
3 Outdoor Units
Example : 5 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch (Y branch)
Ⓒ
: Indoor Units
Ⓓ
: Downward Indoor Unit
Ⓔ
: Connection branch pipe be-
tween Outdoor units: ARCNN31
Ⓕ
: Connection branch pipe be-
tween Outdoor units: ARCNN21
10m or
less
L150m (200 m : Conditional application)
ODU Capacity
Master ≥ Slave1 ≥ Slave 2
l
40m (90 m : Conditional application)
H 110m
Slave2
Slave1
Master
h 40m
h1
4 Outdoor Units
Example : 5 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch (Y branch)
Ⓒ
: Indoor Units
Ⓓ
: Downward Indoor Unit
Ⓔ
: Connection branch pipe be-
tween Outdoor units: ARCNN41
Ⓕ
: Connection branch pipe be-
tween Outdoor units: ARCNN31
Ⓖ
: Connection branch pipe be-
tween Outdoor units : ARCNN21
10m or
less
L150m (200 m : Conditional application)
l
40m (90 m : Conditional application)
H 110m
Slave2
Slave3
Slave1
Master
G
ODU Capacity
Master ≥ Slave1 ≥ Slave 2 ≥ Slave 3
h 40m
h1
Refrigerant piping system
Branch pipe can not be used after header
4 Outdoor Units
Example : 6 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: Header branch
Ⓒ
: Indoor Units
Ⓓ
: Sealing
Ⓔ
: Connection branch pipe be-
tween Outdoor units: ARCNN41
Ⓕ
: Connection branch pipe be-
tween Outdoor units: ARCNN31
Ⓖ
: Connection branch pipe be-
tween Outdoor units : ARCNN21
10m or
less
H 110m
L 200m
40m
Master
Slave3
Slave1
Slave2
ODU Capacity
Master ≥ Slave1 ≥ Slave2 ≥ Slave3
40m
G
G
h1
F
E
F
E
Branch pipe can not be used after header
L 150m(200m : Conditional application)
40m(90m : Conditional application)
L 110m
40
m
Branch pipe can not be used after header
2 Outdoor Units
Example : 5 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch
Ⓒ
: Y branch
Ⓓ
: Indoor Unit
Ⓔ
: Connection branch pipe be-
tween Outdoor units: ARCNN21
Ⓕ
: Header
Ⓖ
: Sealed piping
10m or
less
H 110m
Master
Slave
Master
Slave
L 150m(200m : Conditional application)
40m(90m : Conditional application)
ODU Capacity
Master ≥ Slave
40
m
h1
Master
Slave
Branch pipe can not be used after header
Summary of Contents for multi V ARUV100DTS4