Test Run
66
Outdoor Unit
Solo
-
Heat Pump
Display
Title
Cause of Error
Outdoor unit related error
2
5
1
Outdoor unit Input Voltage High/ Low
Voltage
Outdoor unit input voltage is over 487V or below 270V
2
6
1
Outdoor unit Inverter Compressor Start
Failure
The First Start Failure by Outdoor unit Inverter
Compressor Abnormality
2
8
1
Outdoor unit Inverter DC link High
Voltage
System is turned off by Outdoor unit DC Voltage Over
Charging
2
9
1
Outdoor unit Inverter Compressor Over
Current
Outdoor unit Inverter Compressor Fault OR Drive Fault
3
0
1
Outdoor unit Constant Speed Compressor2
High Discharge Temperature
System is turned off by Outdoor Uunit Constant Speed
Compressor2 High Discharge Temperature
3
2
1
Outdoor unit Inverter Compressor High
Discharge Temperature
System is turned off by Outdoor unit Inverter Compressor
High Discharge Temperature
3
3
1
Outdoor unit Constant Speed
Compressor1 High Discharge Temperature
System is turned off by Outdoor Uunit Constant Speed
Compressor1 High Discharge Temperature
3
4
1
High Pressure of Outdoor Unit
System is turned off by excessive increase of high pressure
of Outdoor unit
3
5
1
Low Pressure of Outdoor unit
System is turned off by excessive decrease of low pressure
of Outdoor unit
3
6
1
Outdoor unit Low Condensing Ratio
Limited
Outdoor unit stayed under low condensing limit for 3 min-
utes
4
0
1
Outdoor unit Inverter Compressor CT
Sensor Fault
Outdoor unit Inverter Compressor CT Sensor open or short
4
1
1
Outdoor unit Inverter Compressor
Discharge Temperature Sensor Fault
Outdoor unit Inverter Compressor Discharge Temperature
Sensor open or short
4
2
1
Outdoor unit Low Pressure Sensor Fault
Outdoor unit Low Pressure Sensor open or short
4
3
1
Outdoor unit High Pressure Sensor Fault
Outdoor unit High Pressure Sensor open or short
4
4
1
Outdoor unit Air Temperature Sensor
Fault
Outdoor unit Air Temperature Sensor open or short
4
5
1
Outdoor unit Heat Exchanger
Temperature Sensor (Front side) Fault
Outdoor unit Heat Exchanger Temperature Sensor(Front
side) open or short
4
6
1
Outdoor unit Suction Temperature Sensor
Fault
Outdoor unit Suction Temperature Sensor open or short
4
7
1
Outdoor unit Constant Speed Compressor1
Discharge Temperature Sensor Fault
Outdoor unit Constant Speed Compressor1 Discharge
Temperature Sensor open or short
4
8
1
Outdoor unit Constant Speed Compressor2
Discharge Temperature Sensor Fault
Outdoor unit Constant Speed Compressor 2 Discharge
Temperature Sensor open or short