38
ENGLISH
Display
Title
Cause of Error
1
0
7
*
Outdoor Unit Fan DC Link Low Voltage Error
Outdoor Unit Fan DC Link Input Voltage is under 50V
1
1
3
*
Outdoor Unit Liquid pipe Temperature Sensor Error
Liquid pipe temperature sensor of Outdoor Unit is open or short
1
1
4
*
Outdoor Unit Subcooling Inlet Temperature
Sensor Error
Outdoor Unit Subcooling Inlet Temperature Sensor Error
1
1
5
*
Outdoor Unit Subcooling Outlet Temperature
Sensor Error
Outdoor Unit Subcooling Outlet Temperature Sensor Error
1
1
6
*
Outdoor Unit Oil Level Sensor Error
Oil Level Sensor of Outdoor Unit is open or short
1
4
5
*
Outdoor unit Main Board - External Board
communication Error
Outdoor unit Main Board - External Board communication Error
1
5
0
*
Outdoor Unit Discharge Superheat not satisfied
Outdoor Unit Compressor Discharge Superheat not satisfied
during 5 Min.
1
5
1
*
Failure of operation mode conversion at Outdoor
Unit
Failure of operation mode conversion at Outdoor Unit
1
5
3
*
Outdoor Unit Heat Exchanger Temperature
Sensor (upper part) Fault
Outdoor Unit Heat Exchanger Temperature Sensor (upper part)
Fault
1
5
4
*
Outdoor Unit Heat Exchanger Temperature
Sensor (lower part) Fault
Outdoor Unit Heat Exchanger Temperature Sensor(lower part)
open or short
1
8
2
*
Outdoor unit External Board Main-Sub Micom
communication Error
Outdoor Unit Main Board Main-Sub Micom communication
failed
1
8
7
*
Hydro - Kit P,HEX bursting error
Inlet water temperature is below 5 degree or water temperature
error during defrosting operation.
1
9
3
*
Outdoor Unit Fan Heatsink High Temperature
System is turned off by Outdoor Unit Fan Heatsink High
Temperature
1
9
4
*
Outdoor Unit Fan Heatsink Temperature Sensor
Fault
Outdoor Unit Fan Heatsink Temperature Sensor open or short
Network error
2
4
2
*
Network error of cntral controller
Communication wiring defect
Outdoor unit related error