12 | PRODUCT DATA
Single Zone Mega W
all Mounted Engineering Manual
'XHWRRXUSROLF\RIFRQWLQXRXVSURGXFWLQQRYDWLRQVRPHVSHFL¿FDWLRQVPD\FKDQJHZLWKRXWQRWL¿FDWLRQ
©
/*(OHFWURQLFV86$,QF(QJOHZRRG&OLIIV1-$OOULJKWVUHVHUYHG³/*´LVDUHJLVWHUHGWUDGHPDUNRI/*&RUS
Nominal
Tons
Unit Model
No.
Hertz Voltage Voltage Range
(Min. to Max.) MCA MOP
Compressor
Quantity
Compressor Motor
RLA
Outdoor Fan Motor Indoor Fan Motor
Cooling
Heating
W
FLA
W
FLA
3/4
LS090HEV2
60 208 - 230
187-253
10.0
15
1
7.0
7.0
43
0.4
30
0.4
1
LS120HEV2
10.0
15
1
7.0
7.0
43
0.4
30
0.4
1-1/2
LS180HEV2
15.0
20
1
10.0
10.0
85
0.4
58
0.4
2
LS240HEV2
15.0
20
1
10.0
10.0
85
0.4
58
0.4
0HJDDQG0HJD92XWGRRU8QLWV
ELECTRICAL DATA
Table 4: 208-230V, 60Hz, 1-Phase Single-Zone Mega System Electrical Data Table.
Table 5: 115V, 60Hz, 1-Phase Single Zone Single-Zone Mega 115V System Electrical Data Table.
Nominal
Tons
Unit Model
No.
Hertz Voltage Voltage Range
(Min
.
to Max.) MCA MOP
Compressor
Quantity
Compressor Motor
RLA
Outdoor Fan Motor Indoor Fan Motor
Cooling
Heating
W
FLA
W
FLA
3/4
LS090HXV
60
115
104-127
13.5
20
1
10.0
10.0
43
0.4
30
0.5
1
LS120HXV
13.5
20
1
10.0
10.0
43
0.4
30
0.5
Electrical Data
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
RLA = Rated Load Amps.
FLA = Full Load Amps.
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
RLA = Rated Load Amps.
FLA = Full Load Amps.