- A place where the unit will be leveled and that can support the
weight of the unit.
- A place where the unit can withstand its vibration.
- A place where service can be easily performed.
Case 2
- Avoid installing air conditioner in such circumstances where cutting
oil mist or iron powder is in suspension in factories, etc.
- Avoid places where inflammable gas is generated, flows in, is stored
or vented.
- Avoid places where sulfurous acid gas or corrosive gas is generated.
- Avoid places near high frequency generators.
Ceiling dimension and hanging bolt location
Install the unit above the ceiling correctly.
POSITION OF SUSPENSION BOLT
Apply a Flexible duct between the unit and duct to absorb unnecessary
vibration.
Case 1
Install the unit leaning to a drainage hole side as a figure for easy water
drainage.
Installation of Unit
Return Air(RA)
Supply Air(SA)
Exhaust Air(EA)
Outdoor Air(OA)
Inspection hatches
600
600
600
600
1006
599
12
04
1140
Hanger bracket
Washe
Washer
Washer
Nut
Double nut
Indoor Unit Installation
- Select and mark the position for fixing bolts.
- Drill the hole for set anchor on the face of ceiling.
- Insert the set anchor and washer onto the suspension bolts for
locking the suspension bolts on the ceiling.
- Mount the suspension bolts to the set anchor firmly.
- Secure the installation plates onto the suspension bolts (adjust level
roughly) using nuts, washers and spring washers.
1 Set anchor
Plate washer
Spring washer
Nut
Suspension
bolts
Old building
New building
2
3
4
5
CAUTION
Tighten the nut and bolt to prevent unit falling.
!
- Attach the hanger bracket to the suspension bolt. Be sure to fix it
securely by using nuts and washers (locally procured) from the upper
and lower sides of the hanger bracket.
- Install the unit after checking the indoor (SA/RA) and outdoor (EA/OA)
in accordance with the figure duct direction label.
- Adjust the height of the unit. (Tighten the double nuts securely.)
- Check the unit is horizontally level.
- Tighten the upper nut.
Drain hole
Drain hole
Duct connecting Flange
Horizontal line
1 de gree or less
1 de gree or less
CAUTION
• Install declination of the ventilation unit
with DX coil is very important for the drain
• Minimum thickness of the insulation for
the connecting pipe shall be 10 mm.
!
CAUTION
Use a level instrument to make sure that
the unit is level and that the tilt (down
slope) to the drain piping connection is
within 1 degree. (Refer to above figures.)
If there is no slope in the direction toward
the drain piping, it may cause water leak-
age.
!