INSTALLATION MANUAL

5

ENGLISH

POSITION OF CONSOLE BOLT

- A place where the unit will be leveled and that can support the

weight of the unit.

- A place where the unit can withstand its vibration.

- A place where service can be easily performed.

Case 2

- Avoid installing air conditioner in such circumstances where cutting

oil mist or iron powder is in suspension in factories, etc.

-  Avoid places where inflammable gas is generated, flows in, is stored

or vented.

- Avoid places where sulfurous acid gas or corrosive gas is generated.

- Avoid places near high frequency generators.

Ceiling dimension and hanging bolt location

Install the unit above the ceiling correctly.

POSITION OF SUSPENSION BOLT

Apply a Flexible duct between the unit and duct to absorb unnecessary
vibration.

Case 1

Install the unit leaning to a drainage hole side as a figure for easy water
drainage.

Installation of Unit

Return Air(RA)

Supply Air(SA)

Exhaust Air(EA)

Outdoor Air(OA)

Inspection hatches

600

600

600

600

1006

599

12

04

1140

Hanger bracket

Washe

Washer

Washer

Nut

Double nut

Indoor Unit Installation

- Select and mark the position for fixing bolts.

- Drill the hole for set anchor on the face of ceiling.

- Insert the set anchor and washer onto the suspension bolts for

locking the suspension bolts on the ceiling.

- Mount the suspension bolts to the set anchor firmly.

- Secure the installation plates onto the suspension bolts (adjust level

roughly) using nuts, washers and spring washers.

1 Set anchor

Plate washer

Spring washer

Nut

Suspension
bolts

Old building

New building

CAUTION

Tighten the nut and bolt to prevent unit falling.

!

- Attach the hanger bracket to the suspension bolt. Be sure to fix it

securely by using nuts and washers (locally procured) from the upper
and lower sides of the hanger bracket. 

- Install the unit after checking the indoor (SA/RA) and outdoor (EA/OA)

in accordance with the figure duct direction label.

- Adjust the height of the unit. (Tighten the double nuts securely.)

- Check the unit is horizontally level. 

- Tighten the upper nut.

Drain hole

Drain hole

Duct connecting Flange

Horizontal line

1 de gree or less

1 de gree or less

CAUTION

• Install declination of the ventilation unit

with DX coil is very important for the drain 

• Minimum thickness of the insulation for

the connecting pipe shall be 10 mm.

!

CAUTION

Use a level instrument to make sure that
the unit is level and that the tilt (down
slope) to the drain piping connection is
within 1 degree. (Refer to above figures.)
If there is no slope in the direction toward
the drain piping, it may cause water leak-
age.

!

Summary of Contents for LZ-H050GXH4

Page 1: ...ive LG Electronics Inc EU Representative LG Electronics European Shared Service Center B V Krijgsman 1 1186 DM Amstelveen The Netherlands Manufacturer LG Electronics Inc Changwon 2nd factory 84 Wanam ro Seongsan gu Changwon si Gyeongsangnam do KOREA VENTILATOR Original instruction QUICK MANUAL AIR CONDITIONER ENGLISH PORTUGUÊS MALTI ITALIANO MAGYAR SLOVENČINA ESPAÑOL БЪЛГАРСKN SLOVENŠČINA FRANÇAIS...

Page 2: ... explo sion or injury Do not open the maintenance cover of the main body during operation Otherwise it may cause electrical shock Use the outdoor air suction hole with the net installed to ensure that birds could not come in Remove estrange things like the bird s nest Otherwise it may cause scarcity of indoor oxygen Install the air intake where polluted air can not be directly sucked in It may cau...

Page 3: ...ods works of art etc It is a consumer ventilator not a precision refrigeration system There is risk of damage or loss of property Do not block the inlet or outlet of air flow It may cause product failure Do not step on or put anyting on the prod uct There is risk of personal injury and failure of product According to IEC 660335 1 This appliance is not intended for use by persons including children...

Page 4: ...h Functions for air conditioner OPERATING INSTRUCTIONS ACCESSORY Name and Function of Remote Controller 1 4 5 7 11 10 9 8 2 3 6 13 12 Please attach the inform label inside of the door Please choose proper language depend on your country Models PQRCVSL0 PQRCVSL0QW 14 15 On Off Button OK Button Back button Up Down Left Right Button Operation display window Model PREMTB100 Available accessories Remot...

Page 5: ...t the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling Mount the suspension bolts to the set anchor firmly Secure the installation plates onto the suspension bolts adjust level roughly using nuts washers and spring washers 1 Set anchor Plate washer Spring washer Nut Suspension bolts Old building New building 2 3 4 5 CAUTION Tighten the nut and bolt to...

Page 6: ...eaker recommended by authorized personnel only MCA Min Circuit Amps A MOP Maximum Over current Protection kW Fan Motor Rated Output kW FLA Full Load Amps A Outdoor Ventilation unit Main power source Switch box ELCB Ventilation unit Power supply Fan motor Model Hz Volts Voltage range MCA MOP kW FLA LZ H050GXN4 LZ H050GXH4 50 220 240 V Max 264 V Min 198V 2 8 8 0 2x2 1 25x2 LZ H080GXN4 LZ H080GXH4 2 ...

Page 7: ...ugh them is clear Make sure no cutting oils or detergents get into the pipes Minimum cross sectional area of conductors Maintenance cover Drain piping Locally procured Drain outlet Duct connecting flange SA Flexible hose Feed Water Water supply piping with strainer Water supply shut off valve Water supply pipe Locally procured Locally procured Locally procured Locally procured Locally procured Cap...

Page 8: ...o Clean and Replace Each Part 1 Cleaning of Air Filter Clean dirt from the air filter using a vacuum cleaner or wash with water if dirt is conspicuous wash with a neutral detergent in lukewarm water After washing with water dry well in the shade Do not expose the air filter to direct sunlight or heat from a fire when drying it If the air filter is damaged purchase it from the service center or pro...

Page 9: ......

Reviews: