Installation
6RMI0-02A
71
Inverter Single
Inverter Single
Inverter Single
Inverter Single
Connecting the Cables
Indoor
Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually
according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal
No. are the same as those of the indoor unit.)
h
Field wiring shall be done such that the current carrying conductors become taut before the earthing conductor
if the cord slips out of the cord anchorage.
• The circuit diagram is a subject to change without notice.
• The earth wire should be longer than the common wires.
• When installing, refer to the circuit diagram on the chassis cover.
• Connect the wires firmly so that they may not be pulled out easily.
• Connect the wires according to color codes, referring to the wiring diagram.
• Connect the wires should be sized per local code.
Provide a circuit breaker between
power source and the outdoor unit as
shown below.
The power cord connected to the outdoor unit should be complied with the following
specifications (UL recognized or CAS certified).
The power connecting cable connected to the indoor and outdoor unit should be complied
with the following specifications (UL recognized or CAS certified).
Air
Conditioner
Main power source
Circuit Breaker
Use a circuit breaker
or time delay fuse.
GN/YL
20m
m
AWG_"B"
Connecting cable (208/230V)
10
±
3m
m
GN/YL
20mm
Power supply cable (208/230V)
AWG_"A"
10
±
3m
m
9k~12k 18k 24k~36k
15 20 25
Circuit
Breaker
(A)
Capacity(Btu/h)
9k/12k/18k 24k/30k/36k
14 12
Power
"A"
Capacity(Btu/h)
9k/12k/16k/18k/24k/30k/36k
18
Power
"B"
Capacity(Btu/h)
When using the separate wire as the power cord, please fix the separate wire into the control box
panel by using tie wrap as the fixture.