PRODUCT DATA | 13
Product Data
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG ” is a registered trademark of LG Corp.
Model Number Nominal Tons Compressor
Qty
Compressor(A)
Cool/Heat
Fan Qty
ODU Fan (A)
IDU Fan (A)
MCA(A)
MOP(A)
LS090HEV1
3/4
1
7.0/7.0
1
0.5
0.5
10
15
LS120HEV1
1
1
7.0/7.0
1
0.5
0.5
10
15
LS180HEV1
1-1/2
1
8.81/8.61
1
0.4
0.4
12
20
LS240HEV1
2
1
10.72/10.28
1
0.4
0.4
15
20
Mega Inverter and Mega 115V Outdoor Units
ELECTRICAL DATA
Table 4: 208-230V, 60Hz, 1-Phase Single-Zone Mega Inverter System Electrical Data Table.
Table 5: 115V, 60Hz, 1-Phase Single Zone Single-Zone Mega 115V System Electrical Data Table.
Model Number Nominal Tons Compressor
Qty
Compressor(A)
Cool/Heat
Fan Qty
ODU Fan(A)
IDU Fan (A)
MCA(A)
MOP(A)
LS090HXV
3/4
1
10/10
1
0.4
0.5
13.5
20
LS120HXV
1
1
10/10
1
0.4
0.5
13.5
20
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.