-28-
To avoid nitrogen entering the refrigerant system in a
liquid state, the top of the cylinder must be higher than
its bottom when you pressurize the system. Usually,
the cylinder is used in a vertical standing position.
1) Air purging
Air and moisture remaining in the refrigerant system
have undesirable effects as indicated below.
• Pressure in the system rises.
• Operating current rises.
• Cooling(or heating) efficiency drops.
• Moisture in the refrigerant circuit may freeze and block
capillary tubing.
• Water may lead to corrosion of parts in the refrigera-
tion system.
Therefore, the indoor unit and tubing between the
indoor and outdoor unit must be leak tested and evacu-
ated to remove any noncondensables and moisture
from the system.
2) Air purging with vacuum pump
1. Preparation
• Check that each tube(both liquid and gas side tubes)
between the indoor and outdoor units have been prop-
erly connected and all wiring for the test run has been
completed. Remove the service valve caps from both
the gas and the liquid side on the outdoor unit. Note
that both the liquid and the gas side service valves on
the outdoor unit are kept closed at this stage.
2. Leak test
• Connect the manifold valve(with pressure gauges)
and dry nitrogen gas cylinder to this service port with
charge hoses.
• Pressurize the system to no more than 150 P.S.I.G.
with dry nitrogen gas and close the cylinder valve
when the gauge reading reached 150 P.S.I.G. Next,
test for leaks with liquid soap.
• Do a leak test of all joints of the tubing(both indoor
and outdoor) and both gas and liquid side service
valves.
Bubbles indicate a leak. Be sure to wipe off the soap
with a clean cloth.
• After the system is found to be free of leaks, relieve
the nitrogen pressure by loosening the charge hose
connector at the nitrogen cylinder. When the system
pressure is reduced to normal, disconnect the hose
from the cylinder.
Lo
Hi
Indoor unit
Outdoor unit
Manifold valve
Charge hose
Nitrogen gas
cylinder(in vertical
standing position)
Pressure
gauge
5. Air Purging
Be sure to use a manifold valve for air purging. If it is
not available, use a stop valve for this purpose. The
"Hi" knob of the manifold valve must always be kept
close.
CAUTION
CAUTION
Summary of Contents for LS-K1863PL
Page 52: ... 52 2 MAIN P W B ASSEMBLY DC PART TOP VIEW 2 MAIN P W B ASM DC BOTTOM VIEW ...
Page 53: ... 53 3 DISPLAY ASSEMBLY 6871A20194 TOP VIEW 6871A30009 TOP VIEW BOTTOM VIEW BOTTOM VIEW ...
Page 54: ...Schematic Diagram TELEPHONE CONTROL MODEL ONLY 54 ...
Page 59: ...P No 3828A20135E February 2003 Printed in Korea ...