background image

Room Air Conditioner

SVC MANUAL(Exploded View)

CAUTION

Before Servicing the unit, read the safety precautions in General SVC manual.
Only for authorized service personnel.

Internal Use Only

http://biz.lgservice.com

MODEL : LS-E0960CL / CM / CN / CD / CS
 

LS-E0960HL / HM / HN / HD / HS

 

LS-F1260CL / CM / CN / CD / CS

 

LS-F1260HL / HM / HN / HD / HS

 

LS-J0760CL / CM / CN / CD / CS

 

LS-J0760HL / HM / HN / HD / HS

 

LS-J0960CL / CM / CN / CD / CS

 

LS-J0960HL / HM / HN / HD / HS

Summary of Contents for LS-E0960CD

Page 1: ...ecautions in General SVC manual Only for authorized service personnel Internal Use Only http biz lgservice com MODEL LS E0960CL CM CN CD CS LS E0960HL HM HN HD HS LS F1260CL CM CN CD CS LS F1260HL HM HN HD HS LS J0760CL CM CN CD CS LS J0760HL HM HN HD HS LS J0960CL CM CN CD CS LS J0960HL HM HN HD HS ...

Page 2: ...lay Function 20 Self diagnosis Function 20 Installation 21 Operation 37 Disassembly of the parts Indoor Unit 39 2 way 3 way Valve 42 Cycle Troubleshooting Guide 49 Electronic Parts Troubleshooting Guide 50 Electronic Control Device 57 Schematic Diagram 59 Exploded View 61 2 Copyright 2008 LG Electronics Inc All right reserved Only for training and service purposes LGE Internal Use Only ...

Page 3: ...g med Heating speed The unit will be stopped after 1 2 3 4 5 6 7 hours The fan is switched to intermittent or irregular operation The fan speed is automatically switched from high to low speed The louver can be set at the desired position or swing up and down automatically Indoor Unit Operation ON OFF by Remote controller Sensing the Room Temperature Room temperature control Starting Current Contr...

Page 4: ...gh CHAOS High 39 C LOW 11 C Down to 18 C Up to 30 C Cooling OFF ON OFF ON Cancel Sleep Mode Timer ON or Timer OFF 1 2 3 4 5 6 7 Off Timer Fan Operates without cooling or heating Auto Operation Mode Heating Operation Mode Operation Mode Selection Fan Speed Selection Room Temperature Display Temperature Setting Setting the Time or timer JET COOL Timer Selection Timer Setting Timer Cancel Sleep Opera...

Page 5: ...t A 2 9 3 8 3 8 4 6 E E R Btu hw 10 14 9 77 9 89 11 2 Indoor 5 5 7 5 7 15 Outdoor 14 14 5 14 5 25 Indoor 802 x 262 x 165 804 x 245 x 153 802 x 262 x 165 900 x 280 x 178 Outdoor 525 x 564 x 265 684 x 624 x 270 Indoor 7 7 7 9 Outdoor 20 25 25 28 Refrigerant R22 g 530 600 530 860 Airflow Direction Control Up Down Remocon Type L C D Wireless Liquid inch mm 1 4 6 35 Gas 3 8 9 52 1 2 12 7 Sleeping Opera...

Page 6: ... 4 0 4 7 E E R Cooling Btu hw 9 33 9 551 9 18 9 677 C O P Heating 3 14 3 062 2 96 3 360 5 5 7 5 7 15 14 14 5 14 5 25 802 x 262 x 165 804 x 245 x 153 802 x 262 x 165 900 x 280 x 178 525 x 564x 265 684 x 624 x 270 810 x 555 x 262 7 7 7 9 21 26 26 35 Refrigerant R22 g 600 610 620 860 Airflow Direction Control Up Down Remocon Type L C D Wireless inch mm 1 4 6 35 3 8 9 52 1 2 12 7 Sleeping Operation Dr...

Page 7: ...te Tubing hole cover Installation plate Right rear piping Left rear piping ø70mm ø70mm 50mm 20mm 20mm 80mm ø70mm A A A A Center Right rear piping Left rear piping Center ø70mm MODEL DIM Unit W mm 802 804 900 H mm 262 245 280 D mm 165 153 178 LS J0760CL HL LS J0960CL HL LS E0960CL HL 12K Btu Series 7K 9K 12K 7K 9K 12K 7K 9K 12K LS J0760CL HL LS J0960CL HL LS E0960CL HL LS F1260CL HL ...

Page 8: ...s LGE Internal Use Only 2 Outdoor Unit 7K 9K LS F1260CL W L2 L3 L1 D H L4 L5 Gas side 3 way valve Liquid side 2 way valve MODEL DIM unit W mm 564 684 H mm 525 640 D mm 281 270 L1 mm 294 305 L2 mm 66 62 L3 mm 374 472 L4 mm 17 16 L5 mm 270 193 7K Btu Series LS E0960CL HL LS J0960CL HL LS F1260CL ...

Page 9: ...s LGE Internal Use Only 3 Outdoor Unit LS F1260HL W D L1 L2 H L3 L4 L5 L6 L7 L8 L9 L10 Liquid side 2 way valve Gas side 3 way valve MODEL 12K Btu Heat Pump DIM unit W mm 801 H mm 555 D mm 262 L1 mm 339 L2 mm 37 L3 mm 543 6 L4 mm 11 4 L5 mm 591 L6 mm 105 L7 mm 105 L8 mm 72 5 L9 mm 86 4 L10 mm 77 ...

Page 10: ...r Ø MAX Max MODEL Piping length Elevation Gas inch Liquid inch m m 3 8 1 4 15 7 INDOOR UNIT OUTDOOR UNIT HEAT EXCHANGE EVAPORATOR HEAT EXCHANGE CONDENSER COMPRESSOR ACCUMU LATOR GAS SIDE 3 WAY VALVE LIQUID SIDE 2 WAY VALVE CAPILLARY TUBE CHECK VALVE Heating Model only COOLING HEATING REVERSING VALVE Heating Model Only 1 2 1 4 15 7 7K 9K Btu SERIES 12K Btu SERIES ...

Page 11: ... BL BR BL BR BL YL OR BK BR GN YL BR THERMISTOR POWER 3854AR2262F RD BL BL GN YL BR GN YL BL BL BL BL YL RD BL YL RD GN YL RD BL BR BR BR H C F PTC C S R OLP 1 L 2 N 3854AR6093B FAN MOTOR COMP CAPACITOR BR YL OUTDOOR WIRING DIAGRAM TERMINAL BLOCK TO INDOOR UNIT SUPPORT VALVE F C H BL R S C COMP FAN MOTOR BL CAPACITOR RD TO INDOOR UNIT OUTDOOR WIRING DIAGRAM RD BR OLP BR YL PILLAR TERMINAL BL 1 L 2...

Page 12: ...TO OUTDOOR UNIT STEP MOTOR STEP MOTOR 1 L 2 N 3 4 GN YL GN YL BL BR BL BR RD BK RD BK BL YL OR BK BR GN YL BR THERMISTOR POWER BL BK BK BL YL YL BR RD BL BR RD GN YL GN YL BL BK RD BR GN YL BL BL PTC 3854AR6093D FAN MOTOR RD BL BR C S R COMP REVERSING VALVE OUTDOOR WIRING DIAGRAM TERMINAL BLOCK TO INDOOR UNIT OLP H C F CAPACITOR 1 L 2 N 3 4 3854AR2262E RD RD RD RD Indoor Unit Outdoor Unit Outdoor ...

Page 13: ...eep timer cancel or appliance operation pause Timer Indicator On while in timer mode on off off when timer mode is completed or canceled Defrost Indicator Off except when hot start during heating mode operation or while in defrost control Cooling Mode Operation When the intake air temperature reaches 0 5 C below the setting temp the compressor and the outdoor fan stop When it reaches 0 5 C above t...

Page 14: ...he outdoor fan is turned on off according to the indoor pipe temp While in defrost control both of the indoor and outdoor fans are turned off Defrost Control While in heating mode operation in order to protect the evaporator pipe of the outdoor unit from freezing reversed to cooling cycle to defrost the evaporator pipe of the outdoor unit Defrost control is available 60 min later since heating mod...

Page 15: ... outdoor fan and the 4 way valve are off and only the indoor fan is operated for 15 seconds Then an operation mode is selected according to the intake air temp at that moment as follows 24 C Inatake Air Temp Fuzzy Operation for Cooling 21 C Inatake Air Temp 24 C Fuzzy Operation for Dehumidification Inatake Air Temp 21 C Fuzzy Operation for Heating If any of the operation modes among cooling dehumi...

Page 16: ... for Heating According to the setting temperature selected by Fuzzy rule when the intake air temp is 3 C or more above the setting temp the compressor is turned off When below the setting temp the compressor is turned on Compressor ON Temp Setting Temp Compressor OFF Temp Setting Temp 3 C At the beginning of Fuzzy mode operation the setting temperature is automatically selected according to the in...

Page 17: ...tops While the appliance is on pause the sleep timer mode cannot be input While in cooling mode operation 30 min later since the start of the sleep timer the setting temperature increases by 1 C After another 30 min elapse it increases by 1 C again When the sleep timer mode is input while in cooling cycle mode the airflow speed of the indoor fan is set to the low When the sleep timer mode is input...

Page 18: ...nce operation the mode before the power failure is kept on the memory and the appliance automatically operates in the mode on the memory The slide switch on the main unit of the appliance should be on the Auto Restarting position in order that the Auto Restarting operation is available Operation Mode that is kept on the memory State of Operation ON OFF Operation Mode Setting Temp Selected Airflow ...

Page 19: ...g Mode Operation 22 C High Speed 21 C Intake Air Temp 24 C Dehumidification Operation 23 C High Speed Intake Air Temp 21 C Heating Mode Operation 24 C High Speed While in forced operation the key input by the remote control has no effect and the buzzer sounds 10 times to indicate the forced operation Remote Control Operation Mode When the remote control is selected by the slide switch on the main ...

Page 20: ...tor Error Indicator When the indoor pipe sensor or the room temperature sensor is open or is shorted the error is indicated To indicate the error the operation LED or the cooling LED flashed at 3 sec interval When the error is cleared the LED stops flashing the operation or cooling LED is on While in appliance pause the error is not indicated Operation Indicator Timer Indicator Sleep Timer Indicat...

Page 21: ...e room will be good A place where drainage can be easily obtained A place where noise prevention is taken into con sideration Do not install the unit near the door way Ensure the spaces indicated by arrows from the wall ceiling fence or other obstacles If an awning is built over the unit to prevent direct sunlight or rain exposure be careful that heat radiation from the condenser is not restricted...

Page 22: ...1 Mount the installation plate on the wall with four Type A screws if mounting the unit on the concrete wall consider using anchor bolts Always mount the Installation plate horizontally by aligning the marking off line by means of the thread and a level 2 Drill the piping hole with 70mm dia holecore drill Line according to the arrows marked on lower the left and the right side of the Installation ...

Page 23: ...nuts mounted on the connection ports of both indoor and outdoor unit onto the copper pipes When the flare nuts are removed from the indoor unit Some gas may leak as some gas is charged to prevent the inside of the pipe from rusting Fit the copper pipe end into the Bar of flare tool about 0 1 0mm higher See illustration Flare the pipe ends 4 Tape the flaring portion to protect it from the dust or d...

Page 24: ...l Pipings 2 Connection of Pipings 1 Remove the installation plate Pull the two marked portion of bottom of the chassis and pull the installation plate out of chas sis 9K Btu Models only 2 Route the drain hose and the indoor tubing For right rear piping 3 Insert the piping the connecting cables and the drain pipe through the piping hole on the wall 4 Connect the piping and the indoor tubing and dra...

Page 25: ...nection later 6 Wrap the tubing the drain hose and the con necting cable with tape 7 Indoor unit installation Hook the indoor unit onto the upper portion of the installation plate Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate Ensure the hooks are properly seated on the installation plate by moving it in left and right CAUTION Take care to arr...

Page 26: ... hose Hook 1 Push 2 Indoor Outdoor Connecting cable Connecting piping Drain pipe For left rear piping 3 Insert the connecting cables the drain pipe and connecting piping through the piping hole on the wall 4 Connect the piping and the indoor tubing and drain hose and drain pipe and place the drain pipe into the chassis Don t connect the cable to the indoor unit Make a small loop for easy connectio...

Page 27: ...p the insulation material around the connect ing portion 7 Wrap the tubing the drain hose and the connect ing cable with tape 8 Indoor unit installation Hook the indoor unit onto the upper portion of installation plate Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate Ensure the hooks are properly seated on the installation plate by moving it lef...

Page 28: ...n the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation Check them and make sure that they are all tightly fastened If they are loose it could give rise to burn out of the wires 4 Specification of power source 5 Confirm that electrical capacity is sufficient 6 See to it that the starting voltage is maintained a...

Page 29: ...wer source and the unit A disconnection device to adequately disconnect all supply lines must be fitted 1 L Terminals on the outdoor unit Terminals on the outdoor unit Terminals on the indoor unit Terminals on the indoor unit 1 L 1 L 1 L 2 N 2 N 2 N 3 4 3 4 2 N BROWN BLUE G Y BLACK RED BROWN BLUE G Y RED BROWN BROWN BLUE BLACK BLACK G Y RED RED G Y BLUE BROWN BLUE GREEN YELLOW BROWN BLUE GREEN YEL...

Page 30: ... the open position horizontally by finger pressure Remove the securing screws To remove the Grille pull lower the left and right side of the grille toward you slightly tilted and lift it straight upward Two tabs on the top inside edge of chassis are clear of their slots 2 Check the drainage Pour a glass of water on the evaporator Ensure if water flows drain hose of indoor unit without any leakage ...

Page 31: ...t Grasp lower the left and the right side of the Grille and engage two tabs on the top inside edge of the grille with two slots on the cabinet s top front edge Press the Grille toward to the cabinet until it will be back into place 1 L Terminals on the outdoor unit Terminals on the outdoor unit Terminals on the indoor unit Terminals on the indoor unit 1 L 1 L 1 L 2 N 2 N 2 N 3 4 3 4 2 N BROWN BLUE...

Page 32: ...he end of the drain outlet should be off the ground Do not dip it into water and fix it on the wall to avoid swinging in the wind 2 Tape the Piping drain hose and Connecting Cable from down to up 3 Form the piping gathered by taping along the exterior wall and fix it onto the wall by saddle or equivalent 2 Tape the Pipings and Connecting cable from down to up 3 Form the pipings gathered by taping ...

Page 33: ...e seconds with a hexagonal wrench and set it free for one minute 7 Set both liquid and gas side valves to open position with the Hexagonal wrench for the unit operation 5 Air Purging of the Piping and Indoor Unit 1 Air purging The air remaining which contains moisture in the refrigeration cycle may cause a malfunction on the compressor 1 Remove the caps from the 2 way and 3 way valves 2 Remove the...

Page 34: ...ure if the pressure indicated on the gauge is as same as that of measured at first time Liquid side Gas side CLOSE CLOSE Indoor unit Outdoor unit Closed Closed NOTE The additional gas for air purping has been charged in the outdoor unit However if the flare connections have not been done correctly and there gas leaks a gas cylinder and the charge set will be needed CAUTION Do not leak the gas in t...

Page 35: ...pe length and the elevation Capicity is based on standard length and maximum allowance length is the basis of reliability Oil trap should be installed per 5 7 meters Numerical value in is for Rotary Comp model CAUTION In case more than 5m Max Piping Length m Capacity Btu h 7 12K 15 7 5 20 18K 30 20 15 10 5 20 24K 30K 30 15 5 30 Max Elevation m Standard Length m Additional Refrig erant g m ...

Page 36: ...n anti vibration rubber 2 Evaluation of the performance 1 Measure the temperature of the intake and dis charge air 2 Ensure the difference between the intake tem perature and the discharge one is more than 8 C Cooling or reversely Heating 1 Connection of power supply 1 Connect the power supply cord to the inde pendent power supply Circuitbreaker is required 2 Prepare the remote controller Insert t...

Page 37: ...peration mode Refet to page 4 ON OFF TIMER BUTTONS Used to set the time of starting and stopping operation TIME SETTING BUTTONS Used to adjust the time TIMER SET CANCEL BUTTONS Used to set the timer when the desired time is obtained and to cancel the Timer operation CHAOS SWING BUTTON Used to stop or start louver movement and set the desired up down airflow direction SLEEP MODE AUTO BUTTON Used to...

Page 38: ...tion mode Refet to page 4 ON OFF TIMER BUTTONS Used to set the time of starting and stopping operation TIME SETTING BUTTONS Used to adjust the time TIMER SET CANCEL BUTTONS Used to set the timer when the desired time is obtained and to cancel the Timer operation CHAOS SWING BUTTON Used to stop or start louver movement and set the desired up down airflow direction SLEEP MODE AUTO BUTTON Used to set...

Page 39: ...h is set to OFF To remove the Grille from the Chassis Set the up and down air discharge louver to open position horizontally by finger pressure Remove the securing screws 9K Btu models 2EA 12K Btu models 3EA To remove the Grille pull the lower left and right side of the grille toward you slightly tilted and lift it straight upward 1 To remove the sensor housing connect earth conductor step motor c...

Page 40: ...ew Pressing the right side of the discharge grille downward slightly unhook the discharge grille Pull the discharge grille out from the chassis carefully Unhook the left side of the discharge grille and pull the discharge grille out from the chassis carefully only LS J series 4 To remove the Evaporator Remove 3 screws securing the evaporator at the left 1EA at the right 2EA Remove 3 screws securin...

Page 41: ...time slightly pull the evaporator toward you until the tab is clear of the slot 5 To remove the Cross Flow Fan Loosen the screw securing the cross flow fan to the fan motor do not remove Lift up the right side of the cross flow fan and the fan motor separate the fan motor from the cross flow fan Remove the left end of the cross flow fan from the self aligning bearing LS J series ...

Page 42: ...osed Open Open clockwise counter clockwise connected manifold gauge Open Open Open with charging cylinder Open Open Open with charging cylinder Open Open Open Open Works Shipping Air purging Installation Operation Pumping down Transfering Evacuation Servicing Gas charging Servicing Pressure check Servicing Gas releasing Servicing 1 2 3 4 5 6 Valve cap Open position Closed position Pin Service port...

Page 43: ...emove the cap from the 3 way valve s service port Using the hexagonal wrench to press the valve core pin discharge for three seconds and then wait for one minute Repeat this three times 5 Use torque wrench to tighten the service port nut to a torque of 1 8kg cm 6 Set the 3 way valve to the back seat 7 Mount the valve stem nuts to the 2 way and 3 way valves 8 Check for gas leakage At this time espe...

Page 44: ...h the push pin to the service port 4 Air purging of the charge hose Open the low pressure valve on the charge set slightly to air purge from the charge hose 5 Set the 2 way valve to the closed position 6 Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 1kg cm2 g 7 Immediately set the 3 way valve to the closed position Do this quickly so that the gauge ends up i...

Page 45: ...r purging the air use a torque wrench to tighten the flare nut on the 2 way valve 4 Check for gas leakage Check the flare connections for gas leakage 5 Discharge the refrigerant Close the valve on the gas cylinder and discharge the refrigerant until the gauge indicates 3 to 5 kg cm2 g 6 Disconnect the charge set and the gas cylinder and set the 2 way and 3 way valves to the open position Be sure t...

Page 46: ...o the service port 3 Open the valve Lo side on the charge set and discharge the refrigerant until the gauge indicates 0 kg cm2 G If there is no air in the refrigerant cycle the pressure when the air conditioner is not running is higher than 1 kg cm2 G discharge the refrigerant until the gauge indicates 0 5 to 1 kg cm2 G if this is the case it will not be necessary to apply a evacuatin Discharge th...

Page 47: ...t the gauge needle has moved toward 76 cmHg vacuum of 4 mmHg or less 3 Close the valve Lo side on the charge set turn off the vacuum pump and confirm that the gauge needle does not move approxima tely 5 minutes after turning off the vacuum pump 4 Disconnect the charge hose from the vacuum pump Vacuum pump oil If the vacuum pump oil becomes dirty or depleted replenish as needed Lo Open Open Vacuum ...

Page 48: ...rant it can be charged with a little at a time approximately 150g each time while operating the air conditioner in the cooling cycle however one time is not sufficient wait approximately 1 minute and then repeat the procedure pumping down pin 4 Immediately disconnect the charge hose from the 3 way valve s service port Stopping partway will allow the gas to be discharged If the system has been char...

Page 49: ...e difference between intake and discharge air depends on room air humidity When the room air humidity is relativery higher temperature difference is smaller When the room air humidity is relatively lower temperature difference is larger 2 Check temperature and pressure of refrigeration cycle Notice 1 The suction pressure is usually 4 5 6 0 kg cm2 G Cooling at normal condition 2 The temperature can...

Page 50: ...s y Fuse Pattern damage Varistor ZNR01J Check the connection housing for contacting Connector related to CN POWER Connector related to CN MOTOR Connector contacting of Outdoor Fan Compressor Display PWB Ass y Check Check each load Indoor Outdoor Fan Motor Compressor Stepping Motor and contacting condition of related connector PCB Board Operation Check Items Power Transformer Outdoor unit Input Vol...

Page 51: ...k the contact of CN DISPI connector When the compressor stopped Indoor Fan is driven by a low speed At this point the wind speed is not controlled by the remote controller When operated in the Sleeping Mode the wind speed is set to the low speed by force Check DISP PWB Ass y Voltage between CN DISP1 DC 5V When the detect switch double key inside the remote controller door is fault it is impossible...

Page 52: ...ion or are not engaged Compressor Outdoor Fan is stopped Check the related circuit of R02H 12 1K R01H 1 0K R04H 6 2K R03H 1 0K Micom No 3 4 Indoor unit Check the indoor temperature sensor is disconnected or not About 10kΩ at 25 C Turn off Main Power Check the electrical wiring diagram of outdoor side Check the abnormal condition for the component of Compressor Outdoor Fan Motor Check the open or s...

Page 53: ...heck the Fuse AC250V T2A Turn ON Main Power Check the related circuit of indoor Fan Motor The pin NO 63 of Micom and the part for driving SSR the input and output signal of IC01M PIN NO 2 15 Check the pattern Check the SSR SSR Open Indoor Fan Motor never operate SSR short Indoor Fan Motor always operates in case of ON or OFF 4 When indoor Fan does not operate The voltage of PIN NO 1 blue and 3 yel...

Page 54: ...N U D Connector Check the soldering condition on PWB of CN U D Connector If there are no problems after above checks Confirm the assembly conditions that are catching and interfering parts in the rotation radial of the Vertical Louver 5 When Vertical Louver does not operate Check the operating circuit of the Vertical Louver Confirm that there is DC 12V between pin RED of CN U D and GND Confirm tha...

Page 55: ... R04H 6 2K R03H 1 0K Micom No 3 4 Check the indoor room temperature is disconnected or not about 10KΩ at 25 C Check the indoor pipe temperature is disconnected or not about 5KΩ at 25 C Turn ON Main Power Check the DC voltage on the PWB ASS Y The details of check are as followings Check point Between Micom NO 62 and GND Between IC01M NO 14 and GND Comp ON DC 5V Below DC 1V Comp OFF DC 0V About DC 1...

Page 56: ...ng and service purposes LGE Internal Use Only Turn off Main Power Check the electrical wiring diagram of outdoor side Check the abnormal condition for the component of Compressor Outdoor Fan Motor 4 way Check the open or short of connecting wires between indoor and outdoor ...

Page 57: ... OR4H OR5H OR6H 1 LS J0760CL 6871AQ2420W 6 8K OPEN 15K 10K 5 1K 2K 2 LS J0760HL 6871AQ2420V 91K 5 1K 15K 10K 5 1K 2K 3 LS J0960CL 6871AQ2420H 6 8K OPEN 15K 200K 200K 39K 4 LS J0960HL 6871AQ2420J 91K 5 1K 15K 200K 200K 39K 5 LS E0960CL S 6871AQ2420A 6 8K OPEN 91K 12K 12K 20K 6 LS F1260CL S 6871AQ2420B 6 8K OPEN 39K 10K 6 8K 12K 7 LS E0960HL S 6871AQ2420C 91K 5 1K 91K 27K 15K 56K 8 LS F1260HL S 6871...

Page 58: ...ght 2008 LG Electronics Inc All right reserved Only for training and service purposes LGE Internal Use Only 2 Display Ass y LS J0760CL HL LS J0960CL HL P NO 6871A30009A LS E0960CL HL LS F1260CL HL P NO 6871Q3265A ...

Page 59: ...G Electronics Inc All right reserved Only for training and service purposes LGE Internal Use Only Schematic Diagram LS J0760CL 6 8K OPEN 15K 10K 5 1K 6 8K 6 8K 6 8K OPEN 15K 200K 200K 2K 39K LS J0960CL Cooling Only Series ...

Page 60: ... 60 Copyright 2008 LG Electronics Inc All right reserved Only for training and service purposes LGE Internal Use Only Heat Pump Series LS J0760HL 200K 39K 200K 15K 10K LS J0960HL ...

Page 61: ...rvice purposes LGE Internal Use Only Exploded View 1 Indoor Unit 1 LS J0760CL HL LS J0960CL HL 733010 3 16 131410 149304 359011 342800 354210 135311 435301 147581 346810 35211B 352150 146811 W0CZZA 263230 W6640A 264110 249951 268711B 249941 135511 152302 135314 267110 135316 268711A ...

Page 62: ...pyright 2008 LG Electronics Inc All right reserved Only for training and service purposes LGE Internal Use Only 2 LS E0960CL HL 4 2 1 3 11 12 9 7 6 5 22 23 10 25 26 24 28 27 13 14 16 17 15 18 19 20 21 8 29 30 ...

Page 63: ... 2008 LG Electronics Inc All right reserved Only for training and service purposes LGE Internal Use Only 3 LS F1260CL HL 10 1 2 5 6 7 8 9 4 3 13 23 20 21 25 24 22 2 22 1 28 26 30 29 27 12 11 14 15 17 18 16 19 31 32 ...

Page 64: ...c All right reserved Only for training and service purposes LGE Internal Use Only 2 Outdoor unit 1 LS J0760CL HL 2 3 4 5 6 A B C D E F G 1 24 29 5 1 5 2 4 3 2 7 27 22 23 15 17 16 26 25 21 13 14 28 8 10 2 10 1 9 1 6 12 11 20 19 18 30 31 32 ...

Page 65: ...nd service purposes LGE Internal Use Only 2 LS E0960CL HL LS J0960CL HL LS F1260CL 437212 435511 W0CZZB 649940 W6640B 649950 561410 552202 552111 552114 567502 552117 554160 148000 550140 552203A 552203B 430410 349480 437210 559010 349600 546810 554031 Appiled for Heating Model ...

Page 66: ...pyright 2008 LG Electronics Inc All right reserved Only for training and service purposes LGE Internal Use Only 3 LS F1260HL 21 20 19 14 31 28 30 29 5 4 8 7 9 10 11 12 6 2 1 23 22 26 18 16 3 15 13 17 24 25 27 ...

Page 67: ...P NO 3828AR7190X JULY 2008 ...

Reviews: