Installation
Installation Manual
25
ENGLISH
ESP Function
Out door
Room Temp
Total on
Central Run
Defrost
Preheat
PQRCUCS0C
FAN
SPEED
MODE
Lo
Med
200
100
Setting the Low wind to 210
Setting the Medium wind to 175
TEMP
TEMP
1
Press the mode button and the temperature
increasing button(
▲
) same time for three
seconds.
2
Set the volume of each fan speed(Low, Medium, Hi)
by using the temperature control button. Press the
fan speed button to select the fan speed.
The value of E.S.P can be adjusted from 1 to 255.
3
If you press the On/Off button while setting the ESP
function, it will be canceled. (The picture on the left
side is the example of setting the Hi wind to ESP
10.)
4
Press the mode button and the temperature
increasing button (
▲
) same time for three
seconds. Then the ESP setting will be activated
after the temperature display flashes three times.
E.S.P function is setting the volume of each fan speed. It is for the convenience of installation. It is
recommended that you should not use this function while using the remote controller.
EX)
❈
The E.S.P value is set at the proper value at the
factory. So it is highly recommended that you should
not change the E.S.P value at your discretion.
Static pressure(mmAq)
Setting value
0
1
2
3
4
Model name
Step(H/M/L)
8.5 CMM(300cfm)
75
84
94
104
114
7.5 CMM(265cfm)
69
77
88
99
110
6.5 CMM(230cfm)
62
71
83
95
106
9.5 CMM(336cfm)
82
90
99
109
118
8.5 CMM(300cfm)
75
84
94
104
114
7.5 CMM(265cfm)
69
77
88
99
110
15 CMM(530cfm)
90
97
105
114
122
13.5 CMM(477cfm)
82
90
99
109
119
11.5 CMM(406cfm)
75
84
93
103
114
AMNW09GB1A0
[LMDN095HV]
AMNW12GB1A0
[LMDN125HV]
AMNW18GB2A0
[LMDN185HV]