Nominal
Tons
Unit Model
No.
Hertz Voltage
Voltage
Range
(Min. to Max.)
MCA MOP Compressor
Quantity
Compressor
Motor RLA
Locked
Rotor
Amps
Outdoor Unit
Fan Motor
Indoor Unit Fan
Motor
W FLA
W.
FLA
Cooling Heating
2 x 2 Four-Way Ceiling Cassettes
1-1/2
LC188HHV4
60
208 - 230
187 - 253
22
30
1
14.5
14.5
23
460 x 1 1.6 x 1
170
0.6
3 x 3 Four-Way Ceiling Cassettes
2
LC249HHV
60
208 - 230
187 - 253
22
30
1
14.5
14.5
23
460 x 1 1.6 x 1
170
0.6
3
LC369HHV
32
40
22
22
33
280 x 2 1.6 x 2
230
1.0
3-1/2
LC429HHV
260
1.3
4
LC489HHV
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
RLA = Rated Load Amps.
FLA = Full Load Amps.
Table 4: Electrical Data.
ELECTRICAL DATA