–25–
Outdoor
Indoor
Control box cover
(On which the Electric
Wiring Connection is put)
Main terminal board
Control terminal board
Cord
clamper
Cover control
A
A
view
Remote
control cord
Connection
cord between
the indoor unit
and the
outdoor unit
Cord clamper
Main
power source
Switch box
Circuit Breaker
Control terminal board
Control box
ELECTRICAL WIRING
Perform the electrical wiring work according to the electrical
wiring connection.
• All wiring must comply with local requirements.
• Select a power source that is capable of supply-
ing the current required by the air conditioner.
• Use a recognized circuit breaker between the
power source and the unit. A disconnection
device to adequately disconnect all supply lines
must be fitted.
• Capacity of circuit breaker
INDOOR UNIT
• Remove the control box cover for elec-
trical connection between the indoor
and outdoor unit.
• Use the cord clamper to fix the cord.
WIRING CONNECTION
OUTDOOR UNIT
• Remove the control cover for wiring con-
nection.
• Use the cord clamper to fix the cord.
• Earthing work
Connect the cable of diameter 1.6mm
2
or more to the earthing terminal provid-
ed in the control box and do earthing.
Please check !!
Capacity
1 Phase
3 Phase
30K BTU/h
30A
-
36K BTU/h
35A
-
42K BTU/h
40A
-
48K BTU/h
-
25A
60K BTU/h
-
25A
72K BTU/h
-
25A
90K BTU/h
-
30A
100K BTU/h
-
30A