Installation Manual
23
ENGLISH
Connecting Pipes to the Indoor Unit
Piping Connection
Connection of the pipes-Outdoor
1. When piping installation work you must be
used the connector.
Connecting pipe size
Indoor Units
Gas side
Liquid side
12, 18 kBtu/h
Ø12.7(1/2")
Ø6.35(1/4")
24, 30, 36 kBtu/h
Ø15.88(5/8")
Ø6.35(1/4")
48 kBtu/h
Ø19.05(3/4")
Ø9.52(3/8")
2. Align the center of the pipings and sufficiently
tighten the flare nut by hand
3. Finally, tighten the flare nut with torque
wrench until the wrench clicks.
■
When tightening the flare nut with torque
wrench, ensure the direction for tightening
follows the arrow on the wrench.
CAUTION: Use two wrenches and
tighten with regular torque.
• In case of 100 kBtu/h Outdoor Unit: Use Short
Tube for connecting 48 kBtu/h indoor unit to
the outdoor unit, not the Branch Distributor.
• In case of 150 kBtu/h Outdoor Unit: Use Y
Connector for connecting 48 kBtu/h indoor
unit to the Branch Distributor.
NOTICE
Torque
wrench
Liquid side piping
Liquid side piping
Gas side piping
B-UNIT
A-UNIT
Outdoor unit
Torque
wrench
Liquid side piping
B-UNIT
A-UNIT
Outdoor unit
Short tube connector
mm
inch
kgf.cm
Ø6.35
1/4
180~250
Ø9.52
3.8
340~420
Ø12.7
1/2
550~560
Ø15.88
5/8
630~820
Ø19.05
3/4
990~1 210
Outside diameter
Torque