Installation Manual
15
Installation of Indoor, Outdoor Unit
Control terminal board
Control box
Control box cover
(On which the Electric
Wiring Connection is put)
A
A
view
Remote
control cord
Connection
cord between
the indoor unit
and the
outdoor unit
Cord clamper
1
1
48K Btu/h
36K Btu/h
Outdoor
Indoor
Main
power source
Switch box
Circuit Breaker
Cover control
Control terminal
board
Control terminal
board
Main terminal
board
Main terminal
board
ELECTRICAL WIRING
INDOOR UNIT
• Remove the control box cover for
electrical connection between the
indoor and outdoor unit.
(Remove screws
➀
.)
• Use the cord clamper to fix the cord.
Perform the electrical wiring work according to the
electrical wiring connection.
WIRING CONNECTION
OUTDOOR UNIT
• Remove the control cover for wiring
connection.
• Use the cord clamper to fix the cord.
• Earthing work
Connect the cable of diameter 1.6mm
2
or more to the earthing terminal
provided in the control box and do
earthing.
Please check !!
Model
1 Phase
L2-C366BA0
35A
L2-C486BA0
50A
• All wiring must comply with local requirements.
• Select a power source that is capable of
supplying the current required by the air
conditioner.
• Use a recognized circuit breaker between the
power source and the unit. A disconnection
device to adequately disconnect all supply
lines must be fitted.
• Capacity of circuit breaker