Heat insulation material: Polyethylene
foam with thickness more than 8 mm.
THE INDOOR UNIT INSTALLA
TION
Flat washer f
or M10
(accessor
y)
Flat washer f
or M10
(accessor
y)
Hanging bolt
(W3
/8 or M10)
Nut
(W3
/8 or M10)
Nut
(W3
/8 or M10)
Spring washer
(M10)
Set screw of paper
model (4 pieces)
Paper model
for installation
Ceiling
board
150mm
Ceiling boar
d
Ceiling
Keep the length of the bolt
from the brack
et to 40mm
Air Conditioner
body
Keep the length of
5~18mm between the
air conditioner bottom
surface and the ceiling
surface
Adjust the
same height
Open the ceiling board
along the outer edge of
the paper model
The following parts is option.
①
Hanging Bolt - W 3/8 or M10
②
Nut - W 3/8 or M10
③
Spring Washer - M10
④
Plate Washer - M10
Drill the piping hole on the wall slightly tilted
to the outdoor side using a Ø 70 hole-core
drill.
Wall
Indoor
Outdoor
Slope gradient for
drain Should be
1/50 ~ 1/100
CA
UTION
Tighten the nut and bolt to prevent unit
falling.
!
Upward
routing
not allo
wed
1/50~1/100
MAX 800
1000~1500
300 or less
Hanging bar
Unit : mm
Unit : mm
- Be sure to execute heat insulation on the
Indoor Unit Drain Piping
- Drain piping must have down-slope (1/50 to
drain piping.
1/100): be sure not to provide up-and-down
slope to prevent reversal flow.
- During drain piping connection, be careful
not to exert extra force on the drain port on
the indoor unit.
- The outside diameter of the drain connection
on the indoor unit is 32mm.
Piping material: Polyvinyl chloride pipe VP-
25 and pipe fittings