7-1-2 DEFROSTING
1. The defrosting is performed each time when the total running time of the compressor reaches 7 hours.
2. After the power is turned on (or restored after a power failure), the defrosting starts when the total running time of the
compressor reaches 4 hours.
3. When the temperature of the defrosting sensor reaches 13 °C or above, the defrosting stops. If the temperature does not
reach 13 °C in 2 hours after the defrosting starts, the defrosting error code is displayed.
(Refer to 7-1-5 Error Diagnostic Mode.)
4. With the defective defrosting sensor (cut or short-circuited wire), the defrosting will not be performed.
7-1-3 SEQUENTIAL OPERATION OF ELECTRIC COMPONENTS
The electric components, such as the comp, defrosting heater, and cooling fan, start sequentially to avoid the noise and
damage to the part, which may result from the simultaneous start of various components on turning the power on or after
the completion of a test.
Condition of Operation
Operating Sequence
If the temp of the defrosting
sensor is 45 °C or above
(For the initial use after the
purchase or grounding)
If the temp of the defrosting
sensor is below 45 °C
(After a power failure or SVC)
- 21 -
POWER
in 0.5 sec
COMP & COOLING FAN
ON
ON
POWER
in 0.5 sec
DEFROSTING
in 10 sec
DEFROSTING
ON
HEATER ON
HEATER OFF
in 0.5 sec
COMP & COOLING FAN
ON
When the power is turned on
Summary of Contents for GR-472
Page 32: ...7 5 MAIN PWB ASSEMBLY AND PARTS LIST 7 5 1 MAIN PWB ASSEMBLY u u GR R472 R522 32 ...
Page 33: ...7 5 2 MAIN PWB ASSEMBLY u u GR S472 S522 33 ...
Page 34: ...7 5 3 REPLACEMENT PARTS LIST u u GR R472 R522 34 ...
Page 35: ...7 5 4 REPLACEMENT PARTS LIST u u GR S472 S522 35 ...
Page 36: ...7 5 5 PWB ASSEMBLY DISPLAY AND PARTS LIST u u GR R472 R522 36 ...
Page 37: ...7 5 6 PWB ASSEMBLY DISPLAY AND PARTS LIST u u GR S472 S522 37 ...
Page 38: ...7 6 1 PWB DIAGRAM u u GR R472 R522 38 ...
Page 39: ... 39 ...
Page 40: ...7 6 2 PWB DIAGRAM u u GR S472 S522 40 ...
Page 41: ... 41 REF TEMP CONTROL ...