4. FASTEN THE SHUTOFF VALVE
Fasten the shutoff valve to the cold water pipe with
the pipe clamp.
5. TIGHTEN THE PIPE CLAMP
Tighten the clamp screws until the sealing washer
begins to swell.
NOTE:
Do not overtighten or you may crush
the tubing.
6. ROUTE THE TUBING
Route the tubing between the cold water line and the
refrigerator.
Route the tubing through a hole drilled in the wall or
floor (behind the refrigerator or adjacent base cabinet)
as close to the wall as possible.
NOTE:
Be sure there is sufficient extra tubing (about
8 feet coiled into 3 turns of about 10 mm diameter) to
allow the refrigerator to move out from the wall after
installation.
7. CONNECT THE TUBING TO THE VALVE
Place the compression nut and ferrule (sleeve)
for copper tubing onto the end of the tubing and
connect it to the shutoff valve. Make sure the tubing is
fully inserted into the valve. Tighten the compression
nut securely.
8. FLUSH OUT THE TUBING
Turn the main water supply on
and flush out the tubing until the
water is clear.
Shut the water off at the water
valve after about one quart of
water has been flushed through
the tubing.
31
CONNECTING THE WATER LINE
Vertical Cold
Water Pipe
Saddle-Type
Shutoff Valve
Pipe Clamp
Washer
Inlet End
Pipe Clamp
Clamp Screw
Saddle-Type
Shutoff Valve
Packing
Nut
Outlet
Valve
Ferrule (sleeve)
Compression
Nut
INSTALLATION INSTRUCTIONS
Install the shutoff valve on the nearest frequently used
drinking water line.
1. SHUT OFF THE MAIN WATER SUPPLY
Turn on the nearest faucet to relieve the pressure on
the line.
2. CHOOSE THE VALVE LOCATION
Choose a location for the valve
that is easily accessible. It is best
to connect into the side of a
vertical water pipe. When it is
necessary to connect into a
horizontal water pipe, make the
connection to the top or side,
rather than at the bottom, to avoid
drawing off any sediment from the water pipe.
3. DRILL THE HOLE FOR THE VALVE
Drill a 1/4” hole in the water
pipe (even if using a self-
piercing valve) using a
sharp bit. Remove any burrs
resulting from drilling the
hole in the pipe. Take care
not to allow water to drain
into the drill. Failure to drill a 1/4 hole may result in
reduced ice production or smaller cubes.
WARNING
Connect to potable water supply only.
Ensure all plumbing is to local requirement.
Summary of Contents for GM-589 Series
Page 37: ...NOTES 37 ...
Page 38: ......