Installation
76
Due to our policy of continuous product innovation, some specifications may change without notice.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
SE Box Wiring: Current Transformer (CT)
a
Internal site net metering CT cable (L1)
b
Internal site net metering CT cable (L2)
c
External site net metering CT connector (L1,L2)
d
PV Generation metering CT connector (two L1)
Home 8 SE Box Wiring : External Site Net Metering CT Connector
No.
Terminals
Recommended Wire Color
Wire Gauge
a
Ext. site net CT L1 +
Black
18 – 14 AWG
b
Ext. site net CT L1 -
White
18 – 14 AWG
c
Ext. site net CT L2 +
Red or Black
18 – 14 AWG
d
Ext. site net CT L2 -
White
18 – 14 AWG
y
If external site net metering CTs are required, refer to "Usage of External CTs" for the exact wiring
requirements for external site net metering.
Home 8 SE Box Wiring PV Generation Metering CT Connector
No.
Terminals
Recommended Wire Color
Wire Gauge
e
PV CT L1 +
Black
18 – 14 AWG
f
PV CT L1 -
White
18 – 14 AWG
g
PV CT L1 +
Black
18 – 14 AWG
h
PV CT L1 -
White
18 – 14 AWG
y
Pin 1 and Pin 3, Pin 2 and Pin 4 are shorted inside of the circuitry. All pins may be used for multiple
CTs for PV generation if required. If only 1 CT is used in the system, please use pins 1-2 or pins 3-4.
y
Twisted cable may improve the CT measuring. If an extended cable is required, please twist.