Service Manual
27
Features of Controller
5. Error Mode & Corrective Method
Error mode
CH01
CH04
CH05
CH16
CH17
CH18
CH19
CH21
CH22
CH02
CH03
Cause of error
OPEN/SHORT of
room temp.
sensor
OPEN/SHORT of
outdoor pipe
sensor
OPEN/SHORT of
indoor pipe temp.
sensor
OPEN/SHORT of
outdoor room
temp. sensor
OPEN of
A_Cycle_Low
Pressure Switch
OPEN of
B_Cycle_Low
Pressure Switch
OPEN of
A_Cycle_High
Pressure Switch
OPEN of
B_Cycle_High
Pressure Switch
Phase Reversal
Error
Phase Loss
Communication
Error
Remark
Sensing condition of error
Voltage of sensing: Over 4.8V
Voltage of sensing: Less than
0.5V
Voltage of sensing: Over 4.8V
Voltage of sensing: Less than
0.5V
1. Check the voltage of "CO1H"
on the remote controller.
2. Check the temp. sensor of
remtote controller.
1. Check the voltage between PIN
1 and 2 of CN-A cycle/CN-B
cycle ON the main PCB.
2. Check the temp. sensor of
remtote controller.
1. Check the voltage between PIN 3
and 4 of CN-A cycle/CN-B cycle.
2. Check the temp. sensor of
indoor pipe.
1. Check the voltage between
PIN 1 and 3 of CN-TEMP
OUT on the main PCB.
2. Check the temp. sensor of
outdoor room.
1. Check Low Pressure Switch
2. Check Refrigerant pressure
1. Check Low Pressure Switch
2. Check Refrigerant pressure
1. Check High Pressure Switch
2. Check Refrigerant pressure
1. Check High Pressure Switch
2. Check Refrigerant pressure
1. Check Power Connection
1. Check Power Connection
1. Check the connecting wire
between main PCB remote
controller.
2. Check the input voltage of
remote-controller.
3. Check the wiring of
remote-controller.
Room
temp.(25°C)
= DC 2.5V
Pipe
temp.(25°C)
= DC 2.5V
Pipe temp.(25°C)
= DC 2.2V
Room
temp.(25°C)
= DC 2.2V
Input voltage of
remote-controller
= DC 12V
Voltage of sensing: Over 4.8V
Voltage of sensing: Less than
0.5V
Voltage of sensing: Over 4.8V
Voltage of sensing: Less than
0.5V
Sensing the Reversal Phase
Sensing the Phase Missing
Sensing the numer of Low pressure
S/W open after power_On
• First time within 1 minute
- 3 times during 30 minutes after
first time sensing
- 6 times until 30 minutes after first
time sensing
Sensing the numer of high pressure
S/W open after power_On
• First time within 1 minute
- 3 times during 30 minutes after
first time sensing
- 6 times until 30 minutes after first
time sensing
Communication interruption
between remote controller and
Main PCB for 3 minutes.
Method of SVC