23
INSTALLATION
ENGLISH
Four-Wire Power Cord
•
A 4-wire connection is required
for all mobile and manufactured
home installations, as well as all
new construction after January 1,
1996.
•
A UL-listed strain relief is required.
•
Use a 30-amp, 240-volt, 4-wire,
UL-listed power cord with #10
AWG-minimum copper conductor
and closed loop or forked
terminals with upturned ends.
1
Remove the terminal block access cover on
the upper back of the dryer.
2
Install a UL-listed strain relief into the power
cord through-hole.
3
Thread a 30-amp, 240-volt, 4-wire, UL-listed
power cord with #10 AWG-minimum copper
conductor through the strain relief.
Terminal Block
UL-Listed Strain
Relief
UL-Listed 4-Wire Power Cord
4
Transfer the dryer’s ground wire from behind
the green ground screw to the center screw of
the terminal block.
5
Attach the two hot leads of the power cord to
the outer terminal block screws.
6
Attach the white neutral wire to the center
screw of the terminal block.
7
Attach the power cord ground wire to the
green ground screw.
8
Tighten all screws securely.
9
Reinstall the terminal block access cover.
Ground
Screw
Power Cord
Ground Wire
Hot (Black) Neutral (White)
Hot (Red)
White Wire
moved from
Ground Screw