10
Room Air Conditioner
Part 2 Functions & Controls
2. Basic Mode Controls
2.1 Cooling Mode
Setting
Temp.
-0.5
°
C(-1
°
F)
+0.5
°
C(1
°
F)
Comp. OFF
Thermo ON
Thermo OFF
INV. Comp.
Frequency
Low
High
Low
High
• Operating frequency of compressor depends on the load condition, like the difference between the room temp. and
the set temp., frequency restrictions.
• If the compressor operates at some frequency, the operating frequency of compressor cannot be changed within 30
seconds. ( not emergency conditions)
• Compressor turned off when
- intake air temperature is in between ±0.5°C(±1°F) of the setting temp. limit for three minutes continuously.
- intake air temperature reaches below 1.0°C(2°F) of the temperature of setting temp..
• Compressors two minutes time delay.
- After compressor off, the compressor can restart minimum 2 minutes later.
2.2 Heating Mode
T1
°
C(T2
°
F).
T2
°
C(T4
°
F).
Comp. OFF
INV. Comp.
Frequency
Low
High
Low
High
Comp. OFF
Setting
Temp.
Thermo ON
Thermo OFF
• Operating frequency of compressor depend on the load condition, The difference between the room temp. and set
temp., frequency restrictions.
• If compressor operates at some frequency, the operating frequency of compressor cannot be changed within 30 sec-
onds.
• Condition of compressor turned off
- When intake air temperature rT2°C(T4°F) above the setting temperature.
• Condition of compressor turned on
- When intake air temperature rT1°C(T2°F) above the setting temperature.
* Condition of indoor fan turned off
- While in compressor on : indoor pipe temp. < 20°C(68°F)
- While in compressor off : indoor pipe temp. < 30°C(86°F)
• While in defrost control, the indoor and outdoor fans are turned off.
• Compressor 2minutes delay
- After compressor off, the compressor can restart minimum 2 minutes later.
• T1 and T2 may be changed by models