6
INSTALLATION OF OUTDOOR UNIT
ENGLISH
- If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that
heat radiation from the condenser is not restricted.
- Ensure that the spaces indicated by arrows around front, back and side of the unit.
- Do not place animals and plants in the path of the warm air.
- Take the air conditioner weight into account and select a place where noise and vibration are
minimum.
- Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
More than
300 mm
Fence or
obstacles
More than
More than
300 mm
300 mm
More than
300 mm
Sunr
oof
More than 700 mm
More than 600 mm
Unit : mm
Installation Places
MODEL
CAPACITY
Pipe Size
Length A (m)
Elevation B (m)
Additional
Refrigerant
(g/m)
Gas
Liquid
Standard
Max.
Standard
Max.
AVUQ60GM2A0
17 kW
Ø 19,05(3/4) Ø 9,52(3/8)
7,5
50
7,5
30
20
Piping length and the elevation
INSTALLATION OF OUTDOOR UNIT
Ceiling Suspended Air conditioner