1. Specification

Indoor

Note:

1. Capacities are based on the following conditions:

Cooling: - Indoor Temperature 27°C(80.6°F) DB/19°C(66.2°F) WB

- Outdoor Temperature 35°C(95°F) DB/24°C(75.2°F) WB

Heating: - Indoor Temperature 20°C(68°F) DB/15°C(59°F) WB

- Outdoor Temperature 7°C(44.6°F) DB/6°C(42.8°F) WB

Piping Length - Interconnecting Piping Length 7.5m

- Level Difference of Zero

2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.

Conversion Formula

kW  = Btu/h x 0.0002931

cfm = CMM x 35.3

Power supply

Ø/V/Hz

Current

A

Fan

Motor type

Fan type

Dimensions (W x H x D)

mm(inch)

Piping

Liquid

mm(inch)

connections

Gas

mm(inch)

Refrigerant control

Power&transmission cable

No. x mm

2

Model

ASNH07GB4W0 

[E07SQ NB0]

ASNH09GB4W0

[E09SQ NB0] 

ASNH12GB4W0 

[E12SQ NB0]

1/ 220~240/ 50

1/ 220~240/ 50

1/ 220~240/ 50

0.15

0.15

0.15

BLDC

BLDC

BLDC

Cross Flow Fan

Cross Flow Fan

Cross Flow Fan

895 x 285 x 205(35.2 x 11.2 x 8.07)

895 x 285 x 205(35.2 x 11.2 x 8.07) 

895 x 285 x 205(35.2 x 11.2 x 8.07)

6.35 (1/4)

6.35 (1/4)

6.35 (1/4)

9.52 (3/8)

9.52 (3/8)

9.52 (3/8)

EEV(in Outdoor unit or BD)

EEV(in Outdoor unit or BD)

EEV(in Outdoor unit or BD)

4*0.75

4*0.75

4*0.75

Summary of Contents for ASNH07GB4W0

Page 1: ...d View MODEL ASNH07GB4W0 E07SQ NB0 ASNH09GB4W0 E09SQ NB0 ASNH12GB4W0 E12SQ NB0 CAUTION Before Servicing the unit read the safety precautions in General SVC manual Only for authorized service personnel Internal Use Only http biz lgservice com ...

Page 2: ...ification may be subject to change without prior notice for purpose of improvement Conversion Formula kW Btu h x 0 0002931 cfm CMM x 35 3 Power supply Ø V Hz Current A Fan Motor type Fan type Dimensions W x H x D mm inch Piping Liquid mm inch connections Gas mm inch Refrigerant control Power transmission cable No x mm2 Model ASNH07GB4W0 E07SQ NB0 ASNH09GB4W0 E09SQ NB0 ASNH12GB4W0 E12SQ NB0 1 220 2...

Page 3: ...rt flare connection Liquid pipe connection port flare connection Cooling Heating Cross Flow fan Th3 Th1 Th4 Th2 LOC Description PCB Connector Th1 Thermistor for sunction air temperature CN TH1 Indoor Th2 Thermistor for evaporator inlet temperature Th3 Thermistor for evaporator outlet temperature CN TH2 Indoor Th4 Thermistor for evaporator middle temperature CN TH3 Indoor ...

Page 4: ...ronics Inc All right reserved Only for training and service purposes LGE Internal Use Only 3 Wiring Diagrams Indoor Unit CN U D1 CN MOTOR1 CN L R1 CN OPTION CN HVB CN INLET MAIN PCB CN LIMIT CN DISP1 CN TH1 CN TH2 CN TH3 CN 12V ...

Page 5: ...47582B 352150 354210 354212 249951 342800 149304 35211B 749740 135311 145200 359011 146811B W50400 733010 135500A 149303 W6640A 268711D 135316 152313 263230B 263230A 268711J 267110 147582A W51620A W51620B Note Please ensure GCSC since the replacement parts may be changed depending upon the buyerʼs request Please check the correct parts in View RPL Replacement Part List on GCSC GCSC Website http ww...

Page 6: ...P NO MFL42201037 OCTOBER 2010 ...