Does the Operating LED of indoor unit blink
when Operation's ON?
Is the Connection between indoor power
relay Pin
➂
and terminal block No. 1 right?
Refer to the self-diagnosis function.
The Outdoor Unit does not operate at all.
Trouble 7
YES
Check the connecting state of connector
NO
NO
Is the connection of cable between indoor
and outdoor unit right?
Indoor
Outdoor
1(Brown)
1(Brown)
2(Blue)
2(Blue)
3(Green/YL)
3(Green/YL)
4(Red)
4(Red)
NO
YES
Is the voltage of Terminal Block
,
in
outdoor Control Box about AC220V /
240V?
Check the Fuse of Outdoor PCB Ass'y.
NO
YES
Is the voltage of NF01J
➀
,
➁
in outdoor
PCB Ass'y about AC220V / 240V when
Operation's ON?
Check the PTC and RY-PWR.
NO
YES
Is the Bridge Diode(BD01S) right?
Check the Bring Diode.
NO
YES
Replace the PCB Ass'y.
NO
Troubleshooting Guide