38
Room Air Conditioner
Operation
• This is operation to preheat the compressor by conducting current through motor coils of the compressor for pre-
venting phenomena that liquid refrigerants are income due to difference between temperature of the outside pipe-
and temperature of the compressor as outdoor temperature becomes low.
• Enter preheat operation of the compressor if meeting
,
,
conditions as below at the same time.
where outdoor temperature is less than 5°C
where discharge temperature of the compressor is more than 15°C
where the compressor turns off
• Release preheat operation if meeting one or more of
,
,
conditions.
where outdoor temperature is more than 5°C
where diacharge temperature of the compressor is more than 25°C
where the compressor turns on
Preheat
1) The buzzer sounds 3 times if pressing the tact switch for 10seconds. If turning off the tack switch in this case, the-
operation LED flickers and existing/additional heat Logic is toggled.
2) Display of operation LED in selection of heat option.
- When selecting additional heat Logic : Flickering numbers of LED; 1 time
- When selecting existing heat Logic : Flickering numbers of LED; 2 times
3) Setting is selectable regardless of operation status (on/off)
Selection of Heat Logic Option
25˚C
15˚C
COMP
Discharge Temerature
Preheat Off
Preheat On