- 60 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
The phenomena in case of connecting error
INDOOR UNIT
Connector Type
Condition
Open and connecting error
Open
Open
Open
Open
Short between terminals
(
and
) of ROOM-TH.
Short between terminals
(
and
) of PIPE-TH.
Short between terminals
• The same as the phenomenon of Outdoor Unit.
• The up/down vane does not operate.
• The up/down vane does not smoothly operate.
• It does not operate with a remote controller.
• The operation indicator blinks once
(on for 0.5 second, off for 3 seconds).
• The compressor operates continuously regardless
of the setting temperature and the variation of room
temperature.
• The operation indicator blinks once
(on for 0.5 second, off for 3 seconds)
• Continuous operation
• The operation indicator blinks once.
• The compressor and the outdoor fan stop.
• The indoor fan speed is low.
• The indoor fan does not operate.
• The operation indicator of Indoor unit blinks 8 times.
CN-DC/DC
CN-MOTOR
CN-UP/DOWN
CN-DISP
CN-TH
Blue
Black
Brown
Red
Phenomena
On for 0.5 second
Off for 3 seconds