22
Outside Unit
Refrigerant piping installation
3 Outside Units
Connecting
branch pipe
Combination specification
Gas pipe
Liquid pipe
ARCNN20
ARCNN30
Slave1 Outside unit
gas pipe
Ø
31.8
Ø
28.58
Ø
28.58
Ø
19.05
Ø
22.2
Ø
28.58
Ø
34.9
Don't cut the pipe less
than 70mm
Blow nitrogen
while brazing
OD28.58
Ø
19.05
Ø
22.2
Ø
38.1
OD34.9
Ø
15.88
OD19.05
Slave1 Outside unit pipe
Ø
12.7
Ø
9.52
Ø
12.7
Ø
15.88
Ø
19.05
Ø
12.7
Ø
22.2
OD19.05
Ø
9.52
OD12.7
Main pipe
Master Outside
unit gas pipe
Ø
38.1
Ø
34.9
Ø
34.9
Ø
28.58
Ø
28.58
Ø
41.3
Don't cut the pipe less
than 70mm
Blow nitrogen
while brazing
OD28.58
Ø
19.05
Ø
22.2
Main pipe
Master Outside unit pipe
Ø
12.7
Ø
19.05
Ø
12.7
Ø
15.88
Ø
22.2
Ø
19.05
Ø
9.52
OD12.7
(unit : mm)
Y branch
A
B
To outdoor unit
To branch piping or indoor unit
A
B
Facing
upwards
Facing
downwards
Within
±
3
°
Within
±
3
°
Viewed from point A
in direction of arrow
/- 10
°