ELECTRICAL WIRING
65
ENGLISH
Display
Title
Cause of Error
6
0
Inverter PCB EEPROM Error of Outdoor
Unit
Access Error of Inverter PCB of Outdoor Unit
6
1
High temperature in outdoor
Cond. Pipe
High temperature in outdoor
Cond. Pipe
6
2
Master Outdoor Unit Inverter Heatsink
High Temperature
System is turned off by Master Outdoor Unit In-
verter Heatsink High Temperature
6
5
Master Outdoor Unit Inverter Heatsink
Temperature Sensor Fault
Master Outdoor Unit Inverter Heatsink Temperature
Sensor open or short
6
7
Outdoor Unit Fan Lock
Restriction of Outdoor Unit
7
1
Converter CT Sensor Error of Outdoor
Unit
Converter CT Sensor open or short of Outdoor Unit
7
3
Instant Over Current(Peak) of Outdoor
Unit PFC
Instant Over Current(Peak) of Outdoor Unit PFC
8
6
Outdoor Unit Main PCB EEPROM Error
Communication Fail Between Outdoor Unit Main
MICOM and EEPROM or omitting EEPROM
1 0 6
Master Outdoor Unit FAN IPM Fault
Error
Instant Over Current at Master Outdoor Unit Fan
IPM
1 1 3
Outdoor Unit Liquid pipe Temperature
Sensor Error
Liquid pipe temperature sensor of Outdoor Unit is
open or short
1 1 5
Outdoor Unit Subcooling Outlet Tem-
perature Sensor Error
Outdoor Unit Subcooling Outlet Temperature Sen-
sor Error
1 4 5
Master outdoor unit Main Board - Exter-
nal Board communication Error
Master outdoor unit Main Board - External Board
communication Error
1 5 1
Failure of operation mode conversion at
Outdoor Unit Outdoor Unit
Failure of operation mode conversion at Outdoor
Unit
Outdoor unit related error
Summary of Contents for ARUV025GSD0
Page 69: ......