Outdoor Unit
Connection method of the connecting cable (Example)
1. Make a hole appropriate for the passage of connection cable through on cap by tool.
2. After knocking out the holes, we recommend you paint the edges and areas around the edges using
the repair paint to prevent rusting
3. Pass the connecting cable through the hole.
4. Properly connect the cable on the terminal block.
5. Fix the connection cable with the cord clamp providing on the unit not to have strain at the terminal.
6. Finally, Fix the cap to the conduit panel.
WARNING
• Loose wiring may cause the terminal to overheat or result in unit malfunction.
• A fire hazard may also exist.
• Therefore, be sure all wiring is tightly connected.
Model name
ARUN076DT2 ARUN096DT2
ARUN115DT2
ARUN134DT2
ARUN154DT2
AWG
14
14
14
12
12
Conduit (inch)
1/2
1/2
1/2
1/2
1/2
Knockout Diameter (inch)
7/8
7/8
7/8
7/8
7/8
Model name
ARUN173DT2 ARUN192DT2
ARUN211DT2
ARUN230DT2
ARUN250DT2 ARUN270DT2
ARUN290DT2
ARUN310DT2
AWG
12
12
12
10
8
8
6
6
Conduit (inch)
1/2
1/2
1/2
1/2
1
1
1
1
Knockout Diameter (inch)
7/8
7/8
7/8
7/8
1-23/64
1-23/64
1-23/64
1-23/64
Model name
ARUN330DT2 ARUN350DT2
ARUN370DT2
ARUN390DT2
ARUN410DT2 ARUN430DT2
ARUN450DT2
ARUN470DT2
AWG
6
6
6
6
4
4
4
4
Conduit (inch)
1
1
1
1
1-1/4
1-1/4
1-1/4
1-1/4
Knockout Diameter (inch)
1-23/64
1-23/64
1-23/64
1-23/64
1-23/32
1-23/32
1-23/32
1-23/32
Model name
ARUN076BT2 ARUN096BT2
ARUN115BT2
ARUN154BT2
ARUN173BT2 ARUN192BT2
ARUN211BT2
ARUN230BT2
AWG
10
10
8
6
6
4
4
4
Conduit (inch)
1/2
1/2
1
1
1
1-1/4
1-1/4
1-1/4
Knockout Diameter (inch)
7/8
7/8
1-23/64
1-23/64
1-23/64
1-23/32
1-23/32
1-23/32
Model name
ARUN250BT2 ARUN270BT2
ARUB290BT2
ARUB310BT2
ARUN330BT2 ARUN350BT2
AWG
2
2
2
2
2
2
Conduit (inch)
1-1/4
1-1/4
1-1/4
1-1/4
1-1/4
1-1/4
Knockout Diameter (inch)
1-23/32
1-23/32
1-23/32
1-23/32
1-23/32
1-23/32
Electrical Wiring