Part 4 Trouble Shooting Guide
7.3 Trouble Shooting for Error Code
7.3.1 Error code 01
Discription
Indoor TH. (thermistor) is short or open
• Indoor TH. is short or open
• Indoor TH. is not connected to the indoor unit PCB assembly
• Damage or defect on the sensing circuit of indoor unit PCB assembly. (R01H, R02H, R03H,
R04H, C01H, C02H)
Supposed
Causes
Yes
No
Indoor TH. is connected to
Indoor unit PCB assembly ?
* Connect to CN-TH1 in indoor
unit PCB assembly.
Indoor TH. is working
properly?
Yes
No
Sensing circuit of indoor
unit PCB is operating properly?
Yes
No
* Check Indoor TH.
- Measure resistance of TH
(air : about 10 k
Ω
at 25
°
C, .
pipe : about 5 k
Ω
at 25
°
C)
- If it is not, replace the thermistor.
* Check soldering state of
R01H ~ R04H, C01H, C02H
- If it is broken, replace indoor unit PCB.
*The indoor unit PCB still has some problem.
* Replace the indoor unit PCB.
Be sure to disconnect the power cable plug from the plug socket before disassembling the
equipment for a repair. Internal components and circuit boards are at main potential when the
equipment is connected to the power cables. This voltage is extremely dangerous and may
cause death or severe injury if come in contact with it.
Be sure to turn off power switch before connect or disconnect connector, or parts damage may
be occurred.