Installation
12
Indoor Unit
DIP Switch Setting
For Multi V Models, DIP switch 1, 2, 6, 8 must be set OFF.
Function
Description
Setting Off
Setting On Default
SW1
Communication
N/A (Default)
-
-
Off
SW2
Cycle
N/A (Default)
-
-
Off
SW3
Group Control
Selection of Master or
Slave
Master
Slave
Off
SW4
Dry Contact
Mode
Selection of Dry Con-
tact
Mode
Wired/Wireless remote
controller
selection of Manual or Auto
operation Mode
Auto
Off
SW5
Installation
Fan continuous
operation
Continuous operation
Removal
-
Off
SW6
Heater linkage
N/A
-
-
Off
SW7
Ventilator link-
age
Selection of Ventilator
linkage
Linkage Removal
Working
Off
Vane selection
(Console)
Selection of up/down
side Vane
Up side + Down side Vane
Up side Vane
Only
Region selec-
tion
Selection tropical
region
General model
Tropical
model
SW8
Etc.
Spare
-
-
Off
CAUTION
1. Indoor Unit
2. Outdoor Unit
In case that the products meet specific conditions, “Auto addressing” function can start automatically
with the improved speed by turning the DIP switch #3 of the outdoor unit and resetting the power.
* Specific conditions:
- All names of the indoor units are ARNU****4.
- The serial number of Multi V super IV (outdoor units) is after October 2013.
DIP switch 7 segment
Outdoor Unit PCB
Outdoor Unit DIP Switch
Summary of Contents for ARNU243TLC4