background image

MULTI V

 

Indoor Unit

10. Installation

52

Wall Mounted Unit (Standard)   

– Never fail to have separate power specially for the air conditioner.
– Provide a circuit breaker switch between power source and the unit.
– Confirm the Specification of power source.
– Confirm that electrical capacity is sufficient.
– Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the 

name plate.

– Confirm that the cable thickness is as specified in the power sources specification.

(Particularly note the relation between cable length and thickness.)

– Do not install the leakage breaker in a place which is wet or moist.

Water or moist may cause short circuit.

– The following troubles would be caused by voltage drop-down.

» Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the 

normal function of a overload protection device.

» Proper starting power is not given to the compressor.

 

10.3.2 Wiring connection

• Connect the wires to the terminals on the control board ind vidually according to the outdoor unit connection.
• Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit 

respectively.

• In case of the system with multiple indoor units, mark each indoor unit as unit A, unit B, etc and be sure the 

terminal board wiring to the outdoor unit and indoor units are properly matched. If wiring and piping between the 

outdoor unit and an indoor unit are mismatched, the system may cause a malfunction.

10.3.3 Clamping of cables

1. Arrange 2 power cables on the control panel.
2. First, fasten the steel clamp with a screw to the inner boss of control panel.
3. For connecting of communication (transmission) cable, put the 0.75mm

2

 cable(or thinner cable) on the clamp 

and tighten it with a plastic clamp to the other boss of the control panel. In case that communication 

(transmission) cable is not needed to connect, fix the other side of the clamp with a screw strongly.

WARNING

   

• Make sure that the screws of the terminal are fixed tightly.
• The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to 

which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly 

fastened. (If they are loose, it could give rise to burn-out of the wires.)

• Make sure to attach the sealing material or (field supplied) to hole of wiring to prevent the infiltration of foreign 

particle from outside. Otherwise a short-circuit may occur inside the electric parts box.

• When clamping the wires, be sure no pressure is applied to the wire connections by using the included clamping 

material to make appropriate clamps. Also, when wiring, make sure the cover on the electric parts box fits snugly 

by arranging the wires neatly and attaching the electric parts box cover firmly. When attaching the electric parts 

box cover, make sure no wires get caught in the edges. Pass wiring through the wiring through holes to prevent 

damage to them.

• Make sure the remote controller wiring, the wiring between the units, and other electrical wiring do not pass 

through the same locations outside of the unit, separating them properly, otherwise electrical noise (external 

static) could cause product malfunction.

 

10.3.4 Wired Remote Controller Installation (Optional)

Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a 

place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature.

Summary of Contents for ARNU15GSJA4

Page 1: ...d MULTI V Indoor Unit 1 List of functions 2 Specifications 3 Dimensions 4 Piping Diagrams 5 Wiring Diagrams 6 Capacity Tables 7 Air Velocity and Temperature Distribution 8 Electric Characteristics 9 Sound Levels 10 Installation ...

Page 2: ...dry operation O Convenience Auto changeover O Heat recovery Auto cleaning O Auto operation artificial intelligence O Heat pump or Cooling only Auto restart operation O Child lock O Forced operation O Group control O Sleep mode O Timer on off O Timer weekly O Two thermistor control O External On Off O Wi Fi O Note 1 O Applied X Not Applied Accessory model name Installed at field ordered and purchas...

Page 3: ...dry operation O Convenience Auto changeover O Heat recovery Auto cleaning O Auto operation artificial intelligence O Heat pump or Cooling only Auto restart operation O Child lock O Forced operation O Group control O Sleep mode O Timer on off O Timer weekly O Two thermistor control O External On Off O Wi Fi O Note 1 O Applied X Not Applied Accessory model name Installed at field ordered and purchas...

Page 4: ...nce Auto changeover O Heat recovery Auto cleaning O Auto operation artificial intelligence O Heat pump or Cooling only Auto restart operation Child lock O Forced operation O Group control O Sleep mode O Timer on off O Timer weekly O Two thermistor control O External On Off O Note 1 O Applied X Not Applied Accessory model name Installed at field ordered and purchased separately by the corresponding...

Page 5: ...back O PDRYCB300 O PDRYCB500 Dry Contact For Modbus O Gateway IDU PI485 PHNFP14A0 Connected with the Indoor Units PSNFP14A0 Connected with the Indoor Units ETC Remote temperature sensor PQRSTA0 Zone controller ABZCA Electronic thermostat AQETC CTI Communication transfer interface PKFC0 CO2 Sensor PES C0RV0 Group control wire PZCWRCG3 0 25m O 2 Remo Control Wire PZCWRC2 0 25m O Extension Wire PZCWR...

Page 6: ...t Body kg lbs 8 5 18 7 8 5 18 7 Shipping kg lbs 11 3 24 9 11 3 24 9 Sound Pressure Levels H M L dB A 30 29 28 32 30 28 Sound Power Levels H M L dB A 54 53 52 54 53 52 Power Supply Ø V Hz 1 220 240 50 1 220 240 50 1 220 60 1 220 60 Refrigerant Control EEV EEV Transmission cable mm 1 0 1 5 2C 1 0 1 5 2C Color White White Note 1 Due to our policy of innovation some specifications may be changed witho...

Page 7: ...ght Body kg lbs 8 5 18 7 8 5 18 7 Shipping kg lbs 11 3 24 9 11 3 24 9 Sound Pressure Levels H M L dB A 34 32 28 37 34 30 Sound Power Levels H M L dB A 55 54 52 55 54 53 Power Supply Ø V Hz 1 220 240 50 1 220 240 50 1 220 60 1 220 60 Refrigerant Control EEV EEV Transmission cable mm 1 0 1 5 2C 1 0 1 5 2C Color White White Note 1 Due to our policy of innovation some specifications may be changed wit...

Page 8: ...Sound Power Levels H M L dB A 58 56 54 Power Supply Ø V Hz 1 220 240 50 1 220 60 Refrigerant Control EEV Transmission cable mm 1 0 1 5 2C Color White Note 1 Due to our policy of innovation some specifications may be changed without notification 2 Wiring cable size must comply with the applicable local and national code And Electric characteristics chapter should be considered for electrical work a...

Page 9: ...16 5 8 16 5 8 Weight Body kg lbs 13 0 28 7 13 0 28 7 Shipping kg lbs 16 0 35 3 16 0 35 3 Sound Pressure Levels H M L dB A 43 39 34 46 41 34 Sound Power Levels H M L dB A 63 57 54 65 60 54 Power Supply Ø V Hz 1 220 240 50 1 220 240 50 1 220 60 1 220 60 Refrigerant Control EEV EEV Transmission cable mm 1 0 1 5 2C 1 0 1 5 2C Color White White Note 1 Due to our policy of innovation some specifications...

Page 10: ...16 6 35 6 16 6 35 6 Sound Pressure Levels H M L dB A 49 44 42 52 47 43 Sound Power Levels H M L dB A Power Supply Ø V Hz 1 220 240 50 1 220 240 50 1 220 60 1 220 60 Refrigerant Control EEV EEV Transmission cable mm 1 0 1 5 2C 1 0 1 5 2C Color White White Note 1 Due to our policy of innovation some specifications may be changed without notification 2 Wiring cable size must comply with the applicabl...

Page 11: ...11 MULTI V Indoor Unit Wall Mounted Unit Standard 3 Dimensions SJ Chassis ARNU05GSJ 4 ARNU07GSJ 4 ARNU09GSJ 4 ARNU12GSJ 4 GGGGGGGGGGGGGGGGGGGARNU15GSJ 4 ...

Page 12: ...MULTI V Indoor Unit 3 Dimensions 12 Wall Mounted Unit Standard SK Chassis ARNU18GSK 4 ARNU24GSK 4 ...

Page 13: ...the installation manual in the product box 2 Unit shall be grounded in accordance with the local regulations or applicable national codes 3 The Unit is powered from the outdoor unit Therefore power cable should be connected with the outdoor unit Note 3 2 1 Left rear piping Right rear piping 43 43 140 150 167 Unit Outline 167 Installation plate ...

Page 14: ...Ø6 35 1 4 ARNU09GSJ 4 Ø12 7 1 2 Ø6 35 1 4 ARNU12GSJ 4 Ø12 7 1 2 Ø6 35 1 4 ARNU15GSJ 4 Ø12 7 1 2 Ø6 35 1 4 ARNU18GSK 4 Ø12 7 1 2 Ø6 35 1 4 ARNU24GSK 4 Ø15 88 5 8 Ø9 52 3 8 ARNU30GSVA4 Ø15 88 5 8 Ø9 52 3 8 ARNU36GSVA4 Ø15 88 5 8 Ø9 52 3 8 LOC Description Th1 Room thermistor Th2 Pipe in thermistor Th3 Pipe out thermistor Heat Exchanger C F F lndoor unit EEV Filter Filter Th3 Th2 Th1 Heating Cooling ...

Page 15: ...indoor status CN DISP2 Display Display of indoor status CN EEV EEV output EEV control output CN U D Step motor Step motor output CN TH1 Room inlet pipe sensor Room and inlet pipe thermistor CN TH2 Outlet pipe sensor Outlet pipe thermistor CN REMO Remote controller Remote control line CN CC Dry contact Dry contact line CN EXT1 External On Off External On Off signal input CN LEAK Refrigerant leak de...

Page 16: ... Display Display of indoor status CN EEV EEV output EEV control output CN U D Step motor Step motor output CN TH1 Room inlet pipe sensor Room and inlet pipe thermistor CN TH2 Outlet pipe sensor Outlet pipe thermistor CN REMO Remote controller Remote control line CN CC Dry contact Dry contact line CN EXT1 External On Off External On Off signal input CN LEAK Refrigerant leak detector Refrigerant lea...

Page 17: ...oor CN DISP1 Display Display of indoor status CN DISP2 Display Display of indoor status CN LEV EEV output EEV control output CN U D Step motor Step motor output CN TH1 Room inlet pipe sensor Room and inlet pipe thermistor CN TH2 Outlet pipe sensor Outlet pipe thermistor CN REMO Remote controller Remote control line CN CC Dry contact Dry contact line CN EXT External On Off External On Off signal in...

Page 18: ... 1 6 2 0 1 8 2 2 1 8 2 4 1 9 2 4 1 8 2 4 1 6 35 1 5 1 5 1 8 1 6 2 0 1 8 2 2 1 8 2 4 1 9 2 4 1 8 2 4 1 6 37 1 5 1 5 1 8 1 6 2 0 1 8 2 2 1 8 2 3 1 8 2 3 1 7 2 4 1 6 39 1 5 1 5 1 8 1 6 2 0 1 8 2 2 1 8 2 2 1 8 2 3 1 7 2 4 1 5 2 8 10 1 9 1 7 2 2 1 9 2 6 2 1 2 8 2 1 3 0 2 2 3 4 2 3 3 7 2 2 12 1 9 1 7 2 2 1 9 2 6 2 1 2 8 2 1 3 0 2 2 3 4 2 3 3 6 2 2 14 1 9 1 7 2 2 1 9 2 6 2 1 2 8 2 1 3 0 2 2 3 4 2 3 3 6 2...

Page 19: ...4 5 3 6 5 2 3 9 5 6 4 0 5 7 3 9 5 8 3 7 6 0 3 4 7 1 10 4 8 4 1 5 7 4 5 6 6 4 9 7 1 5 0 7 6 5 2 8 5 5 4 9 3 5 3 12 4 8 4 1 5 7 4 5 6 6 4 9 7 1 5 0 7 6 5 2 8 5 5 4 9 2 5 3 14 4 8 4 1 5 7 4 5 6 6 4 9 7 1 5 0 7 6 5 2 8 5 5 4 9 1 5 2 16 4 8 4 1 5 7 4 5 6 6 4 9 7 1 5 0 7 6 5 2 8 5 5 4 9 0 5 1 18 4 8 4 1 5 7 4 5 6 6 4 9 7 1 5 0 7 6 5 2 8 5 5 4 8 8 5 1 20 4 8 4 1 5 7 4 5 6 6 4 9 7 1 5 0 7 6 5 2 8 5 5 4 8 ...

Page 20: ... 7 9 12 9 7 4 20 7 0 6 0 8 3 6 6 9 7 7 1 10 4 7 3 11 1 7 6 12 5 7 9 12 7 7 3 21 7 0 6 0 8 3 6 6 9 7 7 1 10 4 7 3 11 1 7 6 12 5 7 9 12 7 7 3 23 7 0 6 0 8 3 6 6 9 7 7 1 10 4 7 3 11 1 7 6 12 5 7 9 12 5 7 1 25 7 0 6 0 8 3 6 6 9 7 7 1 10 4 7 3 11 1 7 6 12 3 7 7 12 3 7 0 27 7 0 6 0 8 3 6 6 9 7 7 1 10 4 7 3 11 1 7 6 12 0 7 6 12 2 7 0 29 7 0 6 0 8 3 6 6 9 7 7 1 10 4 7 3 11 1 7 6 11 9 7 4 12 0 6 9 31 7 0 6...

Page 21: ...17 0 2 0 2 0 2 0 2 0 2 0 2 0 14 7 15 0 2 1 2 1 2 1 2 1 2 1 2 0 12 6 13 0 2 2 2 2 2 2 2 2 2 1 2 1 10 5 11 0 2 3 2 3 2 2 2 2 2 2 2 2 9 5 10 0 2 3 2 3 2 3 2 3 2 3 2 2 8 5 9 1 2 3 2 3 2 3 2 3 2 3 2 2 7 0 7 6 2 4 2 4 2 4 2 4 2 3 2 2 5 0 5 6 2 5 2 5 2 5 2 4 2 3 2 2 3 0 3 7 2 6 2 6 2 5 2 4 2 3 2 2 0 0 0 7 2 7 2 6 2 5 2 4 2 3 2 2 3 0 2 2 2 7 2 7 2 5 2 4 2 3 2 2 5 0 4 1 2 8 2 7 2 5 2 4 2 3 2 2 7 0 6 0 2 8 ...

Page 22: ... 9 3 9 3 9 3 9 3 9 14 7 15 0 4 1 4 1 4 1 4 1 4 1 4 1 12 6 13 0 4 3 4 3 4 3 4 3 4 3 4 3 10 5 11 0 4 5 4 5 4 5 4 5 4 5 4 4 9 5 10 0 4 6 4 6 4 6 4 6 4 6 4 4 8 5 9 1 4 7 4 7 4 7 4 7 4 7 4 4 7 0 7 6 4 8 4 8 4 8 4 8 4 7 4 4 5 0 5 6 5 0 5 0 5 0 4 8 4 7 4 4 3 0 3 7 5 3 5 1 5 0 4 8 4 7 4 4 0 0 0 7 5 3 5 2 5 0 4 8 4 7 4 4 3 0 2 2 5 5 5 3 5 0 4 8 4 7 4 4 5 0 4 1 5 6 5 3 5 0 4 8 4 7 4 4 7 0 6 0 5 6 5 3 5 0 4 ...

Page 23: ...8 7 8 7 8 7 7 12 6 13 0 8 1 8 1 8 1 8 1 8 1 8 1 10 5 11 0 8 5 8 5 8 5 8 5 8 5 8 2 9 5 10 0 8 7 8 7 8 6 8 6 8 6 8 2 8 5 9 1 8 8 8 8 8 8 8 8 8 8 8 2 7 0 7 6 9 1 9 1 9 1 9 0 8 8 8 2 5 0 5 6 9 4 9 4 9 4 9 1 8 8 8 2 3 0 3 7 9 9 9 6 9 4 9 1 8 8 8 2 0 0 0 7 10 1 9 7 9 4 9 1 8 8 8 2 3 0 2 2 10 3 10 0 9 4 9 1 8 8 8 2 5 0 4 1 10 5 10 0 9 4 9 1 8 8 8 2 7 0 6 0 10 6 10 0 9 4 9 1 8 8 8 2 9 0 7 9 10 6 10 0 9 4 ...

Page 24: ...it continuous operation and performance can not be guaranteed When selecting the outdoor units avoid the air temperature range that is not guaranteed continuous operation 4 In accordance with operation limits of outdoor unit applicable range of capacity tables is different 5 Refer to Capacity tables and correction factor in the outdoor unit PDB for the actual performance data of each indoor unit a...

Page 25: ...ure C m 10 8 6 4 2 0 10 8 6 4 2 0 m m m 2 1 0 2 7 2 1 0 2 7 Vertical Louver Center Vertial Louver angle 0 0 3 0 5 1 0 2 0 Top View Discharge angle 35 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 0 3 0 3 0 3 0 5 0 5 1 0 1 0 Vertical Louver Center Vertial Louver angle 0 Air speed 0 3m s Range 8 9m Vertical Louver Left Right Vertial L...

Page 26: ...C m 10 8 6 4 2 0 10 8 6 4 2 0 m m m 2 1 0 2 7 2 1 0 2 7 Vertical Louver Center Vertial Louver angle 0 Top View Discharge angle 55 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s Vertical Louver Center Vertial Louver angle 0 Air speed 0 3m s Range 11 9m Vertical Louver Left Right Vertial Louver angle 50 Air speed 0 3m s Range 12 6m 0 3...

Page 27: ...emperature C m 10 8 6 4 2 0 10 8 6 4 2 0 m m m 2 1 0 2 7 2 1 0 2 7 Vertical Louver Center Vertial Louver angle 0 Top View Discharge angle 35 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s Vertical Louver Center Vertial Louver angle 0 Air speed 0 3m s Range 9 2m Vertical Louver Left Right Vertial Louver angle 50 Air speed 0 3m s Range...

Page 28: ... C m 10 8 6 4 2 0 10 8 6 4 2 0 m m m 2 1 0 2 7 2 1 0 2 7 Vertical Louver Center Vertial Louver angle 0 Top View Discharge angle 55 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s Vertical Louver Center Vertial Louver angle 0 Air speed 0 3m s Range 11m Vertical Louver Left Right Vertial Louver angle 50 Air speed 0 3m s Range 13 2m 0 3 ...

Page 29: ...perature C m 10 8 6 4 2 0 10 8 6 4 2 0 m m m 2 1 0 2 7 2 1 0 2 7 Vertical Louver Center Vertial Louver angle 0 Top View Discharge angle 35 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s Vertical Louver Center Vertial Louver angle 0 Air speed 0 3m s Range 9 6m Vertical Louver Left Right Vertial Louver angle 50 Air speed 0 3m s Range 1...

Page 30: ...re C m 10 8 6 4 2 0 10 8 6 4 2 0 m m m 2 1 0 2 7 2 1 0 2 7 Vertical Louver Center Vertial Louver angle 0 Top View Discharge angle 55 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s Vertical Louver Center Vertial Louver angle 0 Air speed 0 3m s Range 11 8m Vertical Louver Left Right Vertial Louver angle 50 Air speed 0 3m s Range 14m 0 ...

Page 31: ...6 4 2 0 m m 0 3 0 5 1 0 1 5 24 26 28 m m 2 1 0 2 7 2 1 0 2 7 Vertical Louver Center Vertial Louver angle 0 Top View Discharge angle 35 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s Vertical Louver Center Vertial Louver angle 0 Air speed 0 3m s Range 10m Vertical Louver Left Right Vertial Louver angle 50 Air speed 0 3m s Range 14 3m ...

Page 32: ...m 2 1 0 2 7 0 3 0 5 1 0 1 5 0 5 0 3 30 32 26 28 2 1 0 2 7 Vertical Louver Center Vertial Louver angle 0 Top View Discharge angle 55 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s Vertical Louver Center Vertial Louver angle 0 Air speed 0 3m s Range 13m Vertical Louver Left Right Vertial Louver angle 50 Air speed 0 3m s Range 14 3m 0 3...

Page 33: ... 0 m m m m 2 1 0 2 7 2 1 0 2 7 0 3 0 5 1 0 1 5 2 0 24 26 28 Vertical Louver Center Vertial Louver angle 0 Top View Discharge angle 35 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s Vertical Louver Center Vertial Louver angle 0 Air speed 0 3m s Range 11 5m Vertical Louver Left Right Vertial Louver angle 50 Air speed 0 3m s Range 16 7m...

Page 34: ...m m 2 1 0 2 7 2 1 0 2 7 0 3 0 5 1 0 2 0 1 5 30 32 26 28 Vertical Louver Center Vertial Louver angle 0 Top View Discharge angle 55 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s Vertical Louver Center Vertial Louver angle 0 Air speed 0 3m s Range 18m Vertical Louver Left Right Vertial Louver angle 50 Air speed 0 3m s Range 18 8m 0 3 0...

Page 35: ... 8 6 4 2 0 m m m m 2 1 0 2 7 2 1 0 2 7 24 26 22 0 3 0 5 1 0 1 5 Vertical Louver Center Vertial Louver angle 0 Top View Discharge angle 25 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s Vertical Louver Center Vertial Louver angle 0 Air speed 0 3m s Range 10 4m Vertical Louver Left Right Vertial Louver angle 50 Air speed 0 3m s Range 1...

Page 36: ... 2 0 m m m 2 1 0 2 7 2 1 0 2 7 0 3 0 5 1 0 1 5 30 32 26 28 Vertical Louver Center Vertial Louver angle 0 Top View Discharge angle 45 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s Vertical Louver Center Vertial Louver angle 0 Air speed 0 3m s Range 11 6m Vertical Louver Left Right Vertial Louver angle 50 Air speed 0 3m s Range 18 2m ...

Page 37: ... 6 4 2 0 m m m m 2 1 0 2 7 2 1 0 2 7 0 3 1 0 1 5 0 5 24 26 22 Vertical Louver Center Vertial Louver angle 0 Top View Discharge angle 25 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s Vertical Louver Center Vertial Louver angle 0 Air speed 0 3m s Range 11 2m Vertical Louver Left Right Vertial Louver angle 50 Air speed 0 3m s Range 16 ...

Page 38: ...m 2 1 0 2 7 2 1 0 2 7 0 3 0 5 1 0 1 5 0 5 0 3 30 32 26 28 26 28 Vertical Louver Center Vertial Louver angle 0 Top View Discharge angle 45 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s Vertical Louver Center Vertial Louver angle 0 Air speed 0 3m s Range 12 1m Vertical Louver Left Right Vertial Louver angle 50 Air speed 0 3m s Range 1...

Page 39: ... s 2 7m 2m 1m 0m 8m 7m 6m 5m 4m 3m 2m 1m 0m 2 7m 2m 1m 0m 8m 7m 6m 5m 4m 3m 2m 1m 0m 28 28 30 30 32 28 0 5 0 5 0 5 0 5 1 5 2 5 2 5 1 5 0 5 1 0 Discharge angle 35 Cooling Temperature C Air velocity m s 2 7m 2m 1m 0m 8m 7m 6m 5m 4m 3m 2m 1m 0m 2 7m 2m 1m 0m 8m 7m 6m 5m 4m 3m 2m 1m 0m 22 22 22 20 20 0 5 0 5 0 5 3 0 0 5 2 5 1 0 1 5 2 0 Discharge angle 25 Heating Temperature C Air velocity m s 2 7m 2m ...

Page 40: ...A MFA kW FLA Cooling Heating ARNU05GSJ 4 SJ 50 220 240 Max 264 Min 198 0 31 15 0 030 0 25 30 0 30 0 ARNU07GSJ 4 SJ 0 31 15 0 030 0 25 30 0 30 0 ARNU09GSJ 4 SJ 0 31 15 0 030 0 25 30 0 30 0 ARNU12GSJ 4 SJ 0 31 15 0 030 0 25 30 0 30 0 ARNU15GSJ 4 SJ 0 31 15 0 030 0 25 30 0 30 0 ARNU18GSK 4 SK 0 65 15 0 058 0 52 53 0 53 0 ARNU24GSK 4 SK 0 65 15 0 058 0 52 53 0 53 0 ARNU30GSVA4 SV 1 19 15 0 113 0 95 88...

Page 41: ... 4 34 32 28 ARNU12GSJ 4 37 34 30 ARNU15GSJ 4 42 39 32 ARNU18GSK 4 43 39 34 ARNU24GSK 4 46 41 34 ARNU30GSVA4 49 44 42 ARNU36GSVA4 52 47 43 ARNU05GSJ 4 ARNU07GSJ 4 ARNU09GSJ 4 1m 1m Microphone Measuring place Anechoic chamber 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 63 125 250 500 1000 2000 4000 8000 Octave Band Sound Pressure Level dB 20μPa Octave Band Center Frequency Hz NC 15 NC 20 NC 25 NC 3...

Page 42: ...000 4000 8000 Octave Band Sound Pressure Level dB 20μPa Octave Band Center Frequency Hz NC 15 NC 20 NC 25 NC 30 NC 35 NC 40 NC 45 NC 50 NC 55 NC 60 NC 65 Approximate Hearing Threshold High Middle Ǹ Low 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 63 125 250 500 1000 2000 4000 8000 Octave Band Sound Pressure Level dB 20μPa Octave Band Center Frequency Hz NC 15 NC 20 NC 25 NC 30 NC 35 NC 40 NC 45 NC...

Page 43: ...75 NR 25 NR 20 NR 80 NR 85 NR 90 High Middle Ǹ Low 10 20 30 40 50 60 70 80 90 100 125 250 500 1000 2000 4000 8000 Sound Power Level 0dB 10E 6μW m 2 Octave Band Center Frequency Hz NR 70 NR 65 NR 60 NR 55 NR 50 NR 45 NR 40 NR 35 NR 30 NR 75 NR 25 NR 20 NR 80 NR 85 NR 90 High Middle Ǹ Low 10 20 30 40 50 60 70 80 90 100 125 250 500 1000 2000 4000 8000 Sound Power Level 0dB 10E 6μW m 2 Octave Band Cen...

Page 44: ...80 NR 85 NR 90 High Middle Ǹ Low 10 20 30 40 50 60 70 80 90 100 125 250 500 1000 2000 4000 8000 Sound Power Level 0dB 10E 6μW m 2 Octave Band Center Frequency Hz NR 70 NR 65 NR 60 NR 55 NR 50 NR 45 NR 40 NR 35 NR 30 NR 75 NR 25 NR 20 NR 80 NR 85 NR 90 High Middle Ǹ Low 10 20 30 40 50 60 70 80 90 100 125 250 500 1000 2000 4000 8000 Sound Power Level 0dB 10E 6μW m 2 Octave Band Center Frequency Hz N...

Page 45: ...ll should be solid enough to protect it from the vibration The place where the unit is not affected by an electrical noise The place where noise prevention is taken into consideration The place where the maintenance space for product is sufficient There should not be any heat source or steam near the unit Please read the instruction sheets completely before installing the product When the power co...

Page 46: ... be done safely According to product type model line up sales region etc applicability of each chassis could be different According to product type model line up sales region etc applicability of each chassis could be different The lower left and the right side piping of Installation Plate According to product type model line up sales region etc applicability of each chassis could be different SJ ...

Page 47: ...over ྙ ྚ 2 Remove the chassis cover from the unit 3 Pull back the tubing holder 4 Remove pipe port cover and positioning the tubing SV chassis 1 Open the panel of the indoor unit 2 Remove the chassis cover from the unit by loosing 5 screws 3 Pull back the tubing holder 4 Remove pipe port cover and position the piping SV chassis The feature can be changed according to type of model According to pro...

Page 48: ...ping housing section Be sure that the drain hose is located at the lowest side of the bundle Locating at the upper side can cause overflow from the drain pan through the inside of the unit CAUTION If the drain hose is routed inside the room insulate the hose with an insulation material so that dripping from sweating condensation will not damage furniture or floors The feature can be changed accord...

Page 49: ...t Seat the indoor unit on the installation plate 1 Hook the indoor unit onto the upper portion of the installation plate engage the three hooks at the top of the indoor unit with the upper edge of the installation plate Ensure that the hooks areproperly seated on the installation plate by moving it left and right 2 Unlock the tubing holder from the chassis and mount between the chassis and install...

Page 50: ...it left and right 3 Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots clicking sound 4 Finish the assembly by screwing the unit to the installation plate by using two pieces of type C screws And assemble a chassis cover SJ SK chassis Recovery the chassis cover in Original place SV chassis The feature can be changed according to ...

Page 51: ...pable of shutting down the power supply to the entire system must be installed CAUTION After the confirmation of the above conditions prepare the wiring as follows 1 Drill the piping hole with a ø 70mm hole core drill Drill the piping hole at either the right or the left with the holes slightly slanted to the outdoor side 1 The drain hose should point downward for easy drain flow 2 Do not make dra...

Page 52: ... of communication transmission cable put the 0 75mm2 cable or thinner cable on the clamp and tighten it with a plastic clamp to the other boss of the control panel In case that communication transmission cable is not needed to connect fix the other side of the clamp with a screw strongly WARNING Make sure that the screws of the terminal are fixed tightly The screw which fasten the wiring in the ca...

Page 53: ...afts or dead spots behind doors and in corners Hot or cold air from ducts Radiant heat from sun or appliances Concealed pipes and chimneys Uncontrolled areas such as an outside wall behind the remote controller This remote controller is equipped with a seven segment LED display For proper display of the remote controller LED s the remote controller should be installed properly The standard height ...

Reviews: