How to Set E.S.P?
22
Indoor Unit
How to Set E.S.P?
Note: 1. The above table shows the correlation between the air rates and E.S.P.
2. Make sure to check and adjust E.S.P (external static pressure) value after the installa-
tion of the product. Otherwise, there is a risk of weak cooling/heating and condensed
water discharge/drop.
ARNU07GM1A4, ARNU09GM1A4, ARNU12GM1A4
ARNU15GM1A4, ARNU18GM1A4
ARNU24GM1A4
(Unit: CMM)
(Unit: CMM)
Setting
value
Static Pressure (mmAq(Pa))
2.5(25)
4(39)
6(59)
8(78)
10(98)
12(118)
14(137)
15(147)
70
11.3
-
-
-
-
-
-
-
75
12.8
-
-
-
-
-
-
-
80
14.4
11.4
-
-
-
-
-
-
85
15.9
13.2
10.2
-
-
-
-
-
90
17.5
15.0
12.0
-
-
-
-
-
95
19.0
16.7
13.7
10.7
-
-
-
-
100
20.6
18.5
15.5
12.5
-
-
-
-
105
22.1
20.3
17.3
14.3
11.1
-
-
-
110
23.7
22.1
19.0
16.1
13.1
10.0
-
-
115
-
23.8
20.8
17.9
15.1
12.2
-
-
120
-
-
22.6
19.7
17.1
14.3
11.3
-
125
-
-
-
21.5
19.1
16.5
13.6
11.9
130
-
-
-
23.3
21.2
18.7
15.8
14.3
135
-
-
-
-
23.2
20.8
18.0
16.7
140
-
-
-
-
-
23.0
20.3
19.1
145
-
-
-
-
-
-
22.5
21.5
150
-
-
-
-
-
-
-
23.8
Setting
value
Static Pressure (mmAq(Pa))
2.5(25)
4(39)
6(59)
8(78)
10(98)
12(118)
14(137)
15(147)
85
16.8
14.6
-
-
-
-
-
-
90
18.1
15.9
-
-
-
-
-
-
95
19.4
17.2
15.0
-
-
-
-
-
100
20.7
18.5
16.3
13.9
-
-
-
-
105
22.0
19.8
17.7
15.3
13.0
-
-
-
110
23.3
21.1
19.1
16.8
14.6
-
-
-
115
24.6
22.4
20.5
18.3
16.3
14.2
-
-
120
25.9
23.7
21.8
19.7
17.9
15.9
13.3
-
125
-
25.1
23.2
21.2
19.6
17.5
15.2
14.6
130
-
-
24.6
22.7
21.2
19.2
17.1
16.3
135
-
-
-
24.2
22.9
20.9
19.0
18.1
140
-
-
-
-
24.5
22.6
20.9
19.9