Floor Standing _
37
Floor Standing
Floor Standing
13. Installation
13.1.2 Outdoor Unit
• If an awning is built over the unit to prevent direct sunlight or rain exposure, be careful that heat radiation from
the condenser is not restricted.
• There should not be any animals or plants which could be affected by hot air discharged.
• Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles.
- Place that can sufficiently endure the weight and vibration of the outdoor unit and where even installation is pos-
sible.
- Place that has no direct influence of snow or rain
- Place with no danger of snowfall or icicle drop
- Place without weak floor or base such as decrepit part of the building or with a lot of snow accumulation
- Install at a place with fluent water draining to prevent damage from localized heavy rain and avoid frequent flood-
ed area.
• Ensure that the space around the back is more than 300 mm on the opposite side to the PCB side and secure 600 mm
space near the compressor and PCB side of the air conditioner for service.
More than 50cm
(Service space)
300 mm
or more
Fence or
obstacles
600 mm or more
(Service space)
300 mm
or more
700 mm
or more
Sunroof
Fence or
obstacles
More than
More than
350 mm
350 mm
More than
350 mm
Sunr
oof
More than 700 mm
More than 450 mm
Summary of Contents for AP-Q100LFA0
Page 1: ...Floor Standing Cooling Only R410A 50 60Hz 6CSP0 04A Replace 6CSP0 03C P No MFL60778813 ...
Page 15: ...5 Dimensions 12 _ Floor Standing Floor Standing Floor Standing APNQ60GT3E4 PT3 Chassis ...
Page 18: ...5 Dimensions Floor Standing _ 15 Floor Standing Floor Standing U5 Chassis APUQ48GTA0 ...
Page 19: ...5 Dimensions 16 _ Floor Standing Floor Standing Floor Standing U3 Chassis APUQ60GT3E4 ...
Page 20: ...5 Dimensions Floor Standing _ 17 Floor Standing Floor Standing APUQ100LFA0 U7 Chassis ...
Page 25: ...22 _ Floor Standing Floor Standing Floor Standing 7 Wiring Diagrams Models AP Q36GRA0 ...
Page 26: ...Floor Standing _ 23 Floor Standing Floor Standing 7 Wiring Diagrams Models AP Q48GTA0 ...
Page 27: ...24 _ Floor Standing Floor Standing Floor Standing 7 Wiring Diagrams Models AP Q60GT3E4 ...
Page 28: ...Floor Standing _ 25 Floor Standing Floor Standing 7 Wiring Diagrams Models AP Q100LFA0 ...