6
Auxiliary Heat Control
Included Items
If the Auxiliary Heat Control has been installed, then the ESP value has to be set.
For every increase in static pressure by 0.01 inWC, the ESP value should be increased by 1.
If the setting ESP value is inappropriate, the provided safety device will turn off the heater
according to the airflow.
* in.wc = inch Water Column, inAq
(Unit: CFM)
CAUTION
Do not use less than minimum airflow.
There is risk of fire or damage to the product.
!
CAUTION
Use the correctly rated power cable.
There is risk of fire or electric shock.
!
Capacity
(kBtu/h (RT))
Heater Capacity (kW)
3
5
8
10
15
20
12(1.0)
380
380
380
Not available
Not available
Not available
18(1.5)
480
480
480
480
Not available Not available
24(2.0)
480
480
480
480
Not available Not available
30(2.5)
630
630
630
630
Not available Not available
36(3.0) 900
900
900
900
900
900
42(3.5)
1 000
1 000
1 000
1 000
1 000
1 000
48(4.0)
1 000
1 000
1 000
1 000
1 000
1 000
54(4.5)
1 300
1 300
1 300
1 300
1 300
1 300
Capacity
(kBtu/h (RT))
Heater Capacity (kW)
3
5
8
10
15
20
18(1.5)
480
480
480
480
Not available Not available
24(2.0)
480
480
480
480
Not available Not available
36(3.0) 900
900
900
900
900
900
42(3.5)
1 000
1 000
1 000
1 000
1 000
1 000
48(4.0)
1 000
1 000
1 000
1 000
1 000
1 000
7/8 inch
(22.2 mm)
1-23/64 inch
(34.5 mm)
1-23/32 inch
(43.7 mm)
<Knockout diameter>
MODEL
POWER SUPPLY
CAPACITY
(kW @ 208/230 V)
HEATER AMPS.
(Amps @ 208/230 V)
MINIMUM CIRCUIT AMPS.
(Amps @ 208/230 V)
CIRCUIT BREAKER
(Amps @ 208/230 V)
POWER CABLE
(AWG)
SIZE OF
CONDUIT
(inch(mm))
KNOCKOUT
DIAMETER
(inch(mm))
SINGLE
CIRCUIT
DUAL CIRCUIT
SINGLE
CIRCUIT
DUAL CIRCUIT
SINGLE
CIRCUIT
DUAL CIRCUIT
SINGLE
CIRCUIT
DUAL CIRCUIT
L1,L3
L2,L4
L1,L3
L2,L4
L1,L3
L2,L4
L1,L3
L2,L4
ANEH033B1 208/230, 60 Hz, 1 Ph
2.46 / 3
11.8 / 13
-
-
14.8 / 16.3
-
-
20 / 20
-
-
10 / 10
-
-
1/2 (21.3)
7/8 (22.2)
ANEH053B1 208/230, 60 Hz, 1 Ph
4.1 / 5
19.6 /21.7
-
-
24.5 / 27.1
-
-
30 / 30
-
-
10 / 10
-
-
1/2 (21.3)
7/8 (22.2)
ANEH083B2 208/230, 60 Hz, 1 Ph
6.56 / 8
31.6 / 34.8
-
-
40 / 43.5
-
-
50 / 50
-
-
6 / 6
-
-
1 (33.4)
1-23/64 (34.5)
ANEH103B2 208/230, 60 Hz, 1 Ph
8.2 / 10
39.3 / 43.5
-
-
49.1 / 54.3
-
-
60 / 60
-
-
6 / 6
-
-
1 (33.4)
1-23/64 (34.5)
ANEH153B2 208/230, 60 Hz, 1 Ph
12.3 / 15
-
20.7 / 21.7 41.8 / 43.5
-
25.9 / 27.2 52.3 / 54.3
-
30 / 30
60 / 60
-
10 / 10
6 / 6
1-1/4(42.3) 1-23/32 (43.7)
ANEH230B2 208/230, 60 Hz, 1 Ph
16.4 / 20
-
39.4 / 43.5 39.4 / 43.5
-
49.2 / 54.3 49.2 / 54.3
-
60 /60
60 /60
-
6 / 6
6 / 6
1-1/4(42.3) 1-23/32 (43.7)
Available power cable
Multi V
(Unit: CFM)
Single & Multi
Multi V
Heater Capacity(kW)
Static pressure drop (in, wc)
0
0
5
-0.01
10
-0.02
15
-0.04
20
-0.06
Single & Multi
Heater Capacity(kW)
Static pressure drop (in, wc)
Single & Multi (Downflow)
0
0 (0)
3, 5
-0.01 (-0.01)
8, 10
-0.02 (-0.01)
15
-0.03 (-0.01)
20
-0.04 (-0.01)
Auxiliary Heat Control Static pressure drop factors
Minimum airflow by heater capacity