Auxiliary Heat Control

Included Items

If the Auxiliary Heat Control has been installed, then the  ESP value  has to be set. 
For every increase in static pressure by 0.01 inWC, the ESP value should be increased by 1.
If the setting ESP value is inappropriate, the provided safety device will turn off the heater
according to the airflow.
* in.wc = inch Water Column, inAq

(Unit: CFM)

CAUTION

Do not use less than minimum airflow.

There is risk of fire or damage to the product.

!

CAUTION

Use the correctly rated power cable.

There is risk of fire or electric shock.

!

Capacity

(kBtu/h (RT))

Heater Capacity (kW)

3

5

8

10

15

20

12(1.0)

380

380

380

Not available

Not available

Not available

18(1.5) 

480

480

480

480

Not available  Not available 

24(2.0) 

480

480

480

480

Not available  Not available 

30(2.5) 

630

630

630

630

Not available  Not available 

36(3.0) 900

900

900

900

900

900

42(3.5) 

1 000

1 000

1 000

1 000

1 000

1 000

48(4.0) 

1 000

1 000

1 000

1 000

1 000

1 000

54(4.5)

1 300

1 300

1 300

1 300

1 300

1 300

Capacity

(kBtu/h (RT))

Heater Capacity (kW)

3

5

8

10

15

20 

18(1.5) 

480

480

480

480

Not available  Not available 

24(2.0) 

480

480

480

480

Not available  Not available 

36(3.0) 900

900

900

900

900

900

42(3.5) 

1 000

1 000

1 000

1 000

1 000

1 000

48(4.0) 

1 000

1 000

1 000

1 000

1 000

1 000

7/8 inch
(22.2 mm)

1-23/64 inch
(34.5 mm)

1-23/32 inch
(43.7 mm)

<Knockout diameter>

MODEL

POWER SUPPLY

CAPACITY

(kW @ 208/230 V)

HEATER AMPS. 

(Amps @ 208/230 V)

MINIMUM CIRCUIT AMPS. 

(Amps @ 208/230 V)

CIRCUIT BREAKER 

(Amps @ 208/230 V)

POWER CABLE 

(AWG)

SIZE OF

CONDUIT

(inch(mm))

KNOCKOUT

DIAMETER

(inch(mm))

SINGLE

CIRCUIT

DUAL CIRCUIT

SINGLE

CIRCUIT

DUAL CIRCUIT

SINGLE

CIRCUIT

DUAL CIRCUIT

SINGLE

CIRCUIT

DUAL CIRCUIT

L1,L3

L2,L4

L1,L3

L2,L4

L1,L3

L2,L4

L1,L3

L2,L4

ANEH033B1 208/230, 60 Hz, 1 Ph

2.46 / 3

11.8 / 13

-

-

14.8 / 16.3

-

-

20 / 20

-

-

10 / 10

-

-

1/2 (21.3)

7/8 (22.2)

ANEH053B1 208/230, 60 Hz, 1 Ph

4.1 / 5

19.6 /21.7

-

-

24.5 / 27.1

-

-

30 / 30

-

-

10 / 10

-

-

1/2 (21.3)

7/8 (22.2)

ANEH083B2 208/230, 60 Hz, 1 Ph

6.56 / 8

31.6 / 34.8

-

-

40 / 43.5

-

-

50 / 50

-

-

6 / 6

-

-

1 (33.4)

1-23/64 (34.5)

ANEH103B2 208/230, 60 Hz, 1 Ph

8.2 / 10

39.3 / 43.5

-

-

49.1 / 54.3

-

-

60 / 60

-

-

6 / 6

-

-

1 (33.4)

1-23/64 (34.5)

ANEH153B2 208/230, 60 Hz, 1 Ph

12.3 / 15

-

20.7 / 21.7 41.8 / 43.5

-

25.9 / 27.2 52.3 / 54.3

-

30 / 30

60 / 60

-

10 / 10

6 / 6

1-1/4(42.3) 1-23/32 (43.7)

ANEH230B2 208/230, 60 Hz, 1 Ph

16.4 / 20

-

39.4 / 43.5 39.4 / 43.5

-

49.2 / 54.3 49.2 / 54.3

-

60 /60

60 /60

-

6 / 6

6 / 6

1-1/4(42.3) 1-23/32 (43.7)

Available power cable

Multi V

(Unit: CFM)

Single & Multi

Multi V

Heater Capacity(kW)

Static pressure drop (in, wc)

0

0

5

-0.01

10

-0.02

15

-0.04

20

-0.06

Single & Multi

Heater Capacity(kW)

Static pressure drop (in, wc)

Single & Multi (Downflow)

0

0 (0)

3, 5

-0.01 (-0.01)

8, 10

-0.02 (-0.01)

15

-0.03 (-0.01)

20

-0.04 (-0.01)

Auxiliary Heat Control Static pressure drop factors

Minimum airflow by heater capacity

Summary of Contents for ANEH033B1

Page 1: ...efore installing the product Installation work must be performed in accordance with the national wiring standards by authorized personnel only Please retain this installation manual for future reference after reading it thoroughly INSTALLATION MANUAL AIR CONDITIONER MFL66300701 Rev 02_052819 Copyright 1996 2019 LG Electronics Inc All Rights Reserved ENGLISH FRANÇAIS ESPAÑOL ...

Page 2: ...a room Properly insulate any tubing run inside a room to prevent sweating that can cause dripping and water damage to wall and floors in moist or uneven locatinons Use a raised concrete pad or concrete blocks provide a solid level foundation for the outdoor unit This prevents water damage and abnormal vibration in an area with high winds Securely anchor the outdoor unit down with bolts and a metal...

Page 3: ...on Manual 3 ENGLISH 4 Safety Precautions 5 Included Items 6 Minimum airflow by heater capacity 6 Auxiliary Heat Control Static pressure drop factors 6 Available power cable 7 Assembly Diagram 11 Electrical Wiring TABLE OF CONTENTS ...

Page 4: ...is risk of fire or electric shock Always install a dedicated circuit and breaker Improper wiring or installation may cause fire or electric shock Use the correctly rated breaker or fuse There is risk of fire or electric shock Do not modify or extend the power cable There is risk of fire or electric shock If the installation isn t complete electric shock or fire may occur or death or injury can be ...

Page 5: ...Q ty 1 1 1 Model Included Items Unit inch mm Figure Auxiliary Heat Control Included Items 13 1 8 333 7 9 1 2 241 8 11 16 220 2 15 16 75 4 15 16 126 15 3 16 385 8 16 5 16 415 Bi metal Terminal block Heater bracket Relay Dimension Note Image shown above may vary depends on model capacity ...

Page 6: ...0 1 000 1 000 1 000 1 000 1 000 7 8 inch 22 2 mm 1 23 64 inch 34 5 mm 1 23 32 inch 43 7 mm Knockout diameter MODEL POWER SUPPLY CAPACITY kW 208 230 V HEATERAMPS Amps 208 230V MINIMUM CIRCUITAMPS Amps 208 230 V CIRCUITBREAKER Amps 208 230 V POWER CABLE AWG SIZE OF CONDUIT inch mm KNOCKOUT DIAMETER inch mm SINGLE CIRCUIT DUALCIRCUIT SINGLE CIRCUIT DUALCIRCUIT SINGLE CIRCUIT DUALCIRCUIT SINGLE CIRCUI...

Page 7: ...ories If there are no harness you don t need to be remove It may vary depending on the model ENGLISH CN_Pipe out Red CN_Pipe in White Multi V CN_EEV White CN_Motor1 White CN_EEV White CN_Motor1 White CN_Room Yellow Terminal Block Terminal Block CN Out CN Out CN_Motor1 white CN_Motor1 white Single Multi NJ CN_EEV White CN_Motor1 White CN_Pipe out Red CN_Pipe in White CN_Room Yellow Terminal Block C...

Page 8: ...uit Bracket Slot Step 5 Install heater The bracket should be inserted in the provided slot Step 6 Attach the heater to panel using the existing holes and screws Control Box Heater Panel Step 3 Pull out control box Remove heater panel Mounting bracket Step 4 Remove the additional mounting bracket shown in the figure while installing 5 kW and 10 kW heater with NJ chassis ...

Page 9: ...ect power cable to terminal block Connect earth cable to heater panel CN_Pipe out Red CN_Pipe in White Multi V CN_EEV White CN_Motor1 White CN_EEV White CN_Motor1 White CN_Room Yellow Terminal Block Terminal Block CN Out CN Out CN_Motor1 white CN_Motor1 white Heater connector Heater connector Heater connector Single Multi NJ CN_EEV White CN_Motor1 White CN_Pipe out Red CN_Pipe in White CN_Room Yel...

Page 10: ...here would be reduction in heating capacity while defrosting or oil return operation SW6 ON Automatic Heater operation Heater operates automatically according to the heater logic without owner s intervene SW6 OFF Heater manual operation Owner s involvement is required for on off operation But the heater operation would be as per the heater logic WARNING When the wire is exposed the malfunction of ...

Page 11: ...Installation Manual 11 ENGLISH Electrical Wiring Electrical Wiring 1 3 5 kW Heater 2 8 10 kW Heater ...

Page 12: ...12 Auxiliary Heat Control Electrical Wiring 3 15 kW Heater 4 20 kW Heater ...

Page 13: ......

Reviews: