1. Specification

Power supply

Ø, V, Hz

Cooling capacity

kW

Btu/h

Heating capacity

kW

Btu/h

Current Nominal running current

A

Fan

Motor type

Fan type

Motor output x Number of unit

Air flow rate

CMM

(H/M/L)

l/s

Capacitor

μF/Vac

Drive

Coil

Row x column x FPI

mm

Dimensions (WxHxD) Body

mm(inch)

Weight

Body

kg(lbs)

Sound level (H/M/L)

dB(A)+3

Piping

Liquid

mm(inch)

connections

Gas

mm(inch)

Dehumidification rate

l/h

Safety devices

Temperature sensor

Referigerant

Referigerant control

Connectable outdoor unit

Power and transmission interunit cable

No. x AWG

Model

AMNW09GAF11

[LMAN097HVP]

AMNW12GAF11

[LMAN127HVP]

Indoor unit type

ART COOL

1, 208/230, 60

1, 208/230, 60

2.64

3.28

9,000

11,200

3.05

3.90

10,400

13,300

0.2

0.2

BLDC

BLDC

Turbo fan

Turbo fan

24 x 1

24 x 1

7.7/5.9/4.4

8.9/7.3/5.6

128/98/73

148/122/93

-

-

Direct Drive

Direct Drive

2R x 20C x 21

2R x 20C x 21

600 x 600 x 147(23.6 x 23.6 x 5.8) 600 x 600 x 147(23.6 x 23.6 x 5.8)

14.5(32.0)

14.5(32.0)

39 / 35 / 31

42 / 38 / 34

6.35(1/4)

6.35(1/4)

9.52(3/8)

9.52(3/8)

1.20 1.40 

Fuse, Thermal Protector for Fan Motor

Thermistor

Thermistor

R410A

R410A

EEV(in Outdoor unit or BD)

EEV(in Outdoor unit or BD)

Multi F / F DX series

Multi F / F DX series

4 x 18(Including Earth)

4 x 18(Including Earth)

Conversion Formula
kW

= Btu/h 

×

0.0002931

CFM = CMM 

×

35.3

Note:

1. All data are based on the following conditions:

- Cooling Temperature : Indoor 26.7℃(80℉) DB / 19.4℃(67℉) WB

Outdoor 35℃(95℉) DB / 23.9℃(75℉) WB

- Heating Temperature : Indoor 21.1℃(70℉) DB / 15.6℃(60℉) WB

Outdoor 8.33℃(47℉) DB / 6.11℃(43℉) WB

- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.

2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber. 

Therefore, these values can be increased owing to ambient conditions during operation.

Summary of Contents for AMNW09GAF11

Page 1: ...AL Exploded View MODEL AMNW09GAF11 LMAN097HVP AMNW12GAF11 LMAN127HVP CAUTION Before Servicing the unit read the safety precautions in General SVC manual Only for authorized service personnel Internal Use Only http biz lgservice com ...

Page 2: ... 148 122 93 Direct Drive Direct Drive 2R x 20C x 21 2R x 20C x 21 600 x 600 x 147 23 6 x 23 6 x 5 8 600 x 600 x 147 23 6 x 23 6 x 5 8 14 5 32 0 14 5 32 0 39 35 31 42 38 34 6 35 1 4 6 35 1 4 9 52 3 8 9 52 3 8 1 20 1 40 Fuse Thermal Protector for Fan Motor Thermistor Thermistor R410A R410A EEV in Outdoor unit or BD EEV in Outdoor unit or BD Multi F F DX series Multi F F DX series 4 x 18 Including Ea...

Page 3: ...ontrol Electric heater High ceiling operation Auto Elevation Grille Reliability Hot start Self diagnosis Soft dry operation Convenience Auto changeover Auto cleaning Auto operation artificial intelligence Auto Restart Child lock Forced operation Group control Sleep mode Timer on off Timer weekly Two thermistor control Individual controller Wired remote controller Deluxe wired remote controller Sim...

Page 4: ...pipe connection port flare connection Cooling Heating Turbo fan Th3 Th1 Th2 LOC Description PCB Connector Th1 Thermistor for sunction air temperature CN TH1 Indoor Th2 Thermistor for evaporator inlet temperature Th3 Thermistor for evaporator outlet temperature CN TH2 Indoor Refrigerant pipe connection port diameters Model Gas Liquid AMNW09GAF11 LMAN097HVP Ø9 52 Ø6 35 AMNW12GAF11 LMAN127HVP Unit mm...

Page 5: ... Inc All right reserved Only for training and service purposes LGE Internal Use Only 4 Wiring Diagrams CN L1 CN N1 CN COM CN EARTH CN MOTOR1 CN ACDC2 CN TH2 CN TH3 CN TH1 CN UD1 CN LR1 CN D1 CN LR2 CN CC CN ACDC2 CN REMO AC ASM DC ASM ...

Page 6: ... 268711B 268711C 249951 330871 267110 349600 346810 359012 352380 147581 145200B 146811A 145200E 145200D 145200C W3300 352150 35211B 354210 263230A W51620B W51620A 263230C W48300 W6640B W6640A 135510 131111 Note Please ensure GCSC since the replacement parts may be changed depending upon the buyer s request Please check the correct parts in View RPL Replacement Part List on GCSC GCSC Website http ...

Page 7: ... 7 Copyright 2013 LG Electronics Inc All right reserved Only for training and service purposes LGE Internal Use Only P NO MFL68020001 JULY 2013 ...

Reviews: