background image

10

INSTALLATION AND SETTING

ENGLISH

Product installation

The installation and cable connection methods
of AC Ez Touch are as follows.

1

Decide the space to install the controller.

- Before fixing the controller to the wall,

check if it is a suitable location to connect
the controller, RS485 cable, power cable,
and Ethernet cable.

- Determine the wiring direction of the prod-

uct, and remove the knockout structure of
the corresponding direction.

* Method of removing the knockout structure

① 

Cut the rim of the groove part on the
both sides of the knockout structure
using a nipper.

2

Fix the controller's wall installation plate to
the wall above RS485 cable.

3

Connect RS485 cable located at the back-
side of the controller main unit to RS485
connector.

③ 

Tear the knockout structure.

② 

After cutting, bend the knockout structure to
the inward direction & outward director for 2
times, respectively.

• Be careful not to cross wire connec-

tions. RS485 communications are
dependant on correct polarity.

• When the cable is connected in reclama-

tion structure, be careful of the bending
of RS485 communication cable.

CAUTION

!

NOTE

!

Make sure to use a nipper as tool. When
using other tools such as pincers, a sharp
cutting trail remains on the cut surface,
and scratch or notches by the electric-
wire may occur.

<when using a 

nipper>

<when using a 

pincers>

Summary of Contents for AC Ez Touch CACEZA000

Page 1: ...on manual for future reference after reading it thoroughly AC Ez Touch PACEZA000 CACEZA000 Original instructions MFL69306902 Rev 05_050819 Copyright 2015 2019 LG Electronics Inc All Rights Reserved ENGLISH ITALIANO ESPAÑOL FRANÇAIS DEUTSCH ΕΛΛΗΝΙΚΆ ČEŠTINA NEDERLANDS POLSKI LIMBA ROMÂNĂ PORTUGUÊS MAGYAR БЪЛГАРСКИ SRPSKI HRVATSKI SVENSKA NORSK SUOMI DANSK EESTI KEEL MALTI SLOVENČINA SLOVENŠČINA LAT...

Page 2: ...ric shock Install the product that can avoid rain water If water enters into the product it may cause product failure Do not install the product at a place with a lot of moisture If moisture enters the product it may cause product failure Make sure to contact the Supplier or Installation Company for the product installation If someone inexperienced installs the product it may result in fire electr...

Page 3: ...electric shock Use standard parts If unauthorized parts are used it may cause fire electric shock explosion user injury or product failure When the product is flooded do not use power off and contact the Service Company It may cause fire or electric shock Do not impose shock to the product It may cause product failure Do not store or use combustible gas or ignition material near the product It may...

Page 4: ... necessary If non standard adaptor is used it may cause product failure During the transportation of the product be careful not to drop or damage the product It may cause product failure or injury of the transporting person During the wiring do not let dew water insect etc enter the connection part where the cable is extended If an foreign object enters it may cause electric shock or product failu...

Page 5: ...d batteries will help to prevent potential negative consequences for the environment animal and human health For more detail information about disposal of your old batteries please contact your city office waste disposal service or the shop where you purchased the product Also You can contact our LG Support Representative Call center from below Link https www lg com sa_en support con tact telephon...

Page 6: ...TE The image of components or separately sold products may be different from the actual products Item Specifications Power supply DC 12 V Adapter Adapter Input 100 240 V 50 60 Hz 1 2 A Output DC 12 V 3 33 A LCD 5 inch color LCD 800 480 Touch C Type Touch Panel 485 communication Max 1 000 m DI Max 100 m Ethernet 100 Mbps Keyboard Korean English Number Using Temperature 0 C 40 C 32 F 104 F Storage t...

Page 7: ...aptor connection part LAN communication part LAN communication connection port for ethernet connec tion 100 Mbps Support RS 485 communication part 1 port AI DI Input part AI Reserved DI Contact point input dry contact input COM Common GND Reset Button For system restart Name LCD display window Back button Home screen button LAN Communication part RS 485 communication part Reset Button AI Reserved ...

Page 8: ...quipment Step 2 Product installation and RS485 communication connection Install AC Ez Touch and connect RS 485 communication cable Step 3 Connecting cables and power adapter Connect network and other cables and then connect the power adapter Step 4 Air conditioner Ventilation equipment Heating equipment registra tion and group set up Register the connected air conditioner ventilation and heating e...

Page 9: ... method may be different according to the indoor unit product or remote con troller type so set the address by refer ring to the indoor unit product or wired remote controller manual NOTE The maximum communication distance guaranteed by LG Electronics is 1 000 m That is the equipment installed at the farthest location from AC Ez Touch shall be within 1 000 m It is recommended to use the communi ca...

Page 10: ...ing a nipper 2 Fix the controller s wall installation plate to the wall above RS485 cable 3 Connect RS485 cable located at the back side of the controller main unit to RS485 connector Tear the knockout structure After cutting bend the knockout structure to the inward direction outward director for 2 times respectively Be careful not to cross wire connec tions RS485 communications are dependant on ...

Page 11: ...it 6 After matching the hook of the wall mount ing plate installed on the wall and the groove of the product push the product to match the groove When connecting T B after removing the sheath referring to the guide as shown on the picture make sure to connect by inserting a short protecting sleeve into the O ring or U terminal 45 5mm GN YL 20mm 10 3mm sleeve O ring Sheath removal guide Shape of ap...

Page 12: ...lation Heating equipment when there is an emergency in the building When DI port detects a short circuit signal AC Ez Touch stops the operations of all connect ed equipment Regarding emergency stop function it can be used by connecting to the DI port of external powerless contact type on the rear of AC Ez Touch as shown below AI DI COM NOTE Separation sequence is in reverse of installation sequenc...

Page 13: ...s for each menu Detail access rights General user can access all menu displayed in the screen Manager and installer When it enters the setting the manger and installer are verified by pass word Start Home status Home menu Aircon control Vent control Heating Control Schedule Report Setting General user Manager and installer Error Error History Change alarm Energy ...

Page 14: ...function Error display appears on the equipment icon Is the equipments with the error message con nected properly If the equipment are not properly con nected error is displayed Check the equipment connection sta tus Lock cannot be set Cannot use temperature limit setting Cannot user auto Registration function Is the product set up as Slave status In slave state you cannot use each equipment s loc...

Page 15: ...esentative LG Electronics Inc EU Representative Krijgsman 1 1186 DM Amstelveen The Netherlands Manufacturer LG Electronics Inc Changwon 2nd factory 84 Wanam ro Seongsan gu Changwon si Gyeongsangnam do KOREA ...

Reviews: