modbus-rtu iS5 manual.doc
9
Address
NO.
Description
Default
Maximum
Minimum
Unit
5227
FU1 #39
Energy save
0
30
0
%
5232
FU1 #50
ETH select
0
1
0
5233
FU1 #51
ETH 1min
180
200
ETH Cont
%
5234
FU1 #52
ETH Cont
100
150
50
%
5235
FU1 #53
Motor type
0
1
0
5236
FU1 #54
OL level
150
150
30
%
5237
FU1 #55
OL time
100
300
0
0.1sec
5238
FU1 #56
OLT select
1
1
0
5239
FU1 #57
OLT level
180
200
30
%
523A
FU1 #58
OLT time
600
600
0
0.1sec
523B
FU1 #59
Stall prev.
0
7
0
523C
FU1 #60
Stall level
180
250
30
%
< FU2 Group >
Address
NO.
Description
Default
Maximum
Minimum
Unit
5307 FU2
#07 Dwell freq
500
maxFreq
StartFreq
0.01Hz
5308
FU1 #08
Dwell time
0
100
0
0.1sec
530A FU2
#10
Jump freq
0
1
0
530B FU2
#11
jump lo 1
1000
jump Hi 1
StartFreq
0.01Hz
530C FU2#12
jump Hi 1
1500
maxFreq
jump Lo 1
0.01Hz
530D FU2
#13
jump lo 2
2000
jump Hi 2
StartFreq
0.01Hz
530E FU2
#14
jump Hi 2
2500
maxFreq
jump Lo 2
0.01Hz
530F FU2
#15
jump lo 3
3000
jump Hi 3
startFreq
0.01Hz
5310 FU2
#16
jump Hi 3
3500
maxFreq
jump Lo 3
0.01Hz
5311
FU2 #17
Start Curve
40
100
1
%
5312
FU2 #18
End Curve
40
100
1
%
5313
FU2 #19
Trip select
0
3
0
BIT
5314 FU2
#20 Power-on run
0
1
0
5315 FU2
#21 RST restart
0
1
0
5316 FU2
#22 Speed Search
0
15
0
BIT
5317 FU2
#23 SS Sup-Curr
100
200
80
5318 FU2
#24 SS P-gain
100
9999
0
5319 FU2
#25
SS I-gain
1000
9999
0
531A FU2
#26 Retry number
0
10
0
531B FU2
#27 Retry delay
10
600
0
0.1sec
531E FU2#30 Motor select
0
9
0
531F FU2#31 Pole number
4
12
2
5320 FU2
#32 Rated-Slip (Note4)
1000 0 0.01Hz
All manuals and user guides at all-guides.com