GENERAL INSTRUCTION GUIDE
EUROTHERM 2204 FM APPROVED LIMIT CONTROLLERS
INDUSTRIAL OVENS
TO CHANGE ENGINEERING UNITS (° F TO ° C):
Press the
PAGE
button until you see
ACCS
in the upper portion of display and
LIST
in the lower portion.
Press the
SCROLL
button and the display will show
CODE
in the upper portion of the display and
“
0
”
in
the lower display. Press the
UP
arrow to change the
“
0
”
to the number
“
1
”
.
Press the
SCROLL
button and the display will show
GOTO
in the upper display and
OPER
in the lower
display.
Change
OPER
to
CONF
by pressing the
UP
arrow button.
Press the
SCROLL
button and the display will now show
CONF
in the upper display and
“
0
”
in the
lower.
Change the
“
0
”
to a
“
2
”
using the
UP
arrow.
Press the
PAGE
button until you see
INST
in the upper display and
CONF
in the lower display.
Press the
SCROLL
button and you will see
UNITS
in the upper display and
°
F
or
°
C
in the lower display
depending on what the unit is set for. Press the
UP
arrow until Engineering units desired is shown.
Press the
PAGE
button until upper display says
EXIT
and lower display says
NO
. Change the
NO
to
YES
instrument will cycle power and reset.