6 TROUBLESHOOTING / FAQ
Problem Solution
1. LCD not illuminated
• Check to make sure all connections are
wired properly
• Test the voltage being supplied to the
meter using an AC voltmeter
• Remove fuses and test with ohmmeter
2. Load LED not flashing
• Verify CT connections and orientations
• Make sure there is sufficient load to draw a
significant
current
• Test the voltage being supplied to the
meter and ensure phases are connected
to correct location on MMU terminal block
3. Registered consumption low
• Check to make sure the reverse phase
arrow is not shown on the LCD
•
Double-check
CT
orientations
• Make sure that current and voltage
connections are in phase.
• Check power connections and fuses
4. Counter isn’t incrementing
• Verify the Load LED is working
• On Mini Meters, verify that counter wires
are connected to COUNTER terminals
Q: Can voltage input wires and current sensing leads be routed through the
same conduit?
A:
Yes, provided you are using Leviton supplied CTs. Alternate CTs must have
18 AWG min. wires with at least 300 VAC insulation rating.
Q: Can digital output wires be routed through the same conduit as voltage
input and current sensing wires?
A:
No. In accordance with NEC and UL requirements, Class 2 wiring (digital outputs)
must be separated from Class 1 wiring.
Q: I still can’t get my meter to work, what now?
A:
Contact technical support via phone or on our website given in the following
section.
21
WEB
VERSION
Summary of Contents for mini meter MMU
Page 1: ...Mini Meter MMU Installation Manual PK A3244 10 02 0A WEB VERSION...
Page 2: ...WEB VERSION...
Page 22: ...Unit minicompteurs multiples Manuel d installation PK A3244 10 02 0A WEB VERSION...
Page 42: ...Mini Medidor MMU Manual de Instalaci n PK A3244 10 02 0A WEB VERSION...
Page 64: ...2018 Leviton Mfg Co Inc PK A3244 10 02 0A WEB VERSION...