TROUBLESHOOTING
•
The Power Extender is not powered
- Circuit breaker is OFF.
- Power wires are not connected properly.
•
The load does not turn ON, but the Power Extender is powered
- The dimmer is OFF.
- The dimmer air gap switch is activated.
- The dimmer is connected to a separate circuit, and the circuit breaker is OFF.
- Dimmer is mis-wired
• Control Neutral (from dimmer) wire is not connected to the Neutral of the Line pair feeding the
dimmer.
•
No full range dimming
- Remove wallplate if necessary and ensure the Power Extender trim adjusment
(refer to Figure 3)
is
set to its fully counter-clockwise (ccw) minimum level.
DI-000-PE200-00A-Pilot
TABLE 2
Cat. No. PE200-7, 277V – For use with Advance
Transformer 277V Mark X™ Dimmable Ballasts
TABLE 1
Cat. No. PE200-1, 120V – For use with
Advance Mark X™ 120V Dimming Ballasts
Used if Dimmer/Switch has Neutral connection (
Power
Extender
D3206/08
Controller/Dimmer
Hot (Black)
(Load)
Neutral (White)
(120VAC)
Green
Ground
LOAD
INPUT
OUTPUT
Neutral
Neutral
Load
Load
Line
Line
NEUTRAL
NEUTRAL
LO
AD
HO
T
SWITCH
HO
T
CONTR
OL
MARK X™
DIMMABLE
BALLAST
Black
OR
White
120V Mark X™
Type Dimmer
Green
Ground
)
Wiring Diagram 1A
120V Single Feed Wiring Application w/Mark X™ Ballast
Wiring Diagram 1B
120V Dual Feed Wiring Application w/Mark X™ Ballast
Used if Dimmer/Switch has Neutral connection (
Power
Extender
D3206/08
Controller/Dimmer
Hot (Black)
Hot (Black)
(Load)
Neutral 2 (White)
Neutral 1 (White)
Line 1 (120VAC)
Line 2 (120VAC)
Green
Ground
LOAD
MARK X™
DIMMABLE
BALLAST
Black
White
Neutral
Load
Line
OR
120V Mark X™
Type Dimmer
Green
Ground
)
Neutral
Load
Line
NEUTRAL
NEUTRAL
LO
AD
HO
T
SWITCH
HO
T
CONTR
OL
INPUT
OUTPUT
Used if Dimmer/Switch has Neutral connection (
Power
Extender
D3206/08
Controller/Dimmer
Hot (Black)
(Load)
Neutral (White)
(120VAC)
Green
Ground
LOAD
Neutral
Neutral
Load
Load
Line
Line
NEUTRAL
NEUTRAL
LO
AD
HO
T
SWITCH
HO
T
CONTR
OL
120V Hi-lume®
BALLAST
Orange
Black
OR
White
120V Mark X™
Type Dimmer
Green
Ground
INPUT
OUTPUT
)
Used if Dimmer/Switch has Neutral connection (
Power
Extender
D3206/08
Controller/Dimmer
Hot (Black)
Hot (Black)
(Load)
Neutral 2 (White)
Neutral 1 (White)
Line 1 (120VAC)
Line 2 (120VAC)
Green
Ground
LOAD
White
Neutral
Load
Line
OR
120V Mark X™
Type Dimmer
Green
Ground
120V Hi-lume®
BALLAST
Orange
Black
INPUT
OUTPUT
)
Neutral
Load
Line
NEUTRAL
NEUTRAL
LO
AD
HO
T
SWITCH
HO
T
CONTR
OL
Wiring Diagram 2A
120V Single Feed Wiring Application w/Hi-lume
®
Ballast
Wiring Diagram 2B
120V Dual Feed Wiring Application w/Hi-lume
®
Ballast
Used if Dimmer/Switch has Neutral connection (
Power
Extender
D3206/08
Controller/Dimmer
Hot (Black)
Hot (Black)
(Load)
Neutral 2 (White)
Neutral 1 (White)
Line 1 (120VAC)
Line 2 (277VAC)
Green
Ground
LOAD
277V MARK X™
DIMMABLE
BALLAST
Black
White
Neutral
Load
Line
OR
120V Mark X™
Type Dimmer
Green
Ground
)
Neutral
Load
Line
NEUTRAL
NEUTRAL
LO
AD
HO
T
SWITCH
HO
T
CONTR
OL
INPUT
OUTPUT
Used if Dimmer/Switch has Neutral connection (
Power
Extender
D3206/08
Controller/Dimmer
Hot (Black)
Hot (Black)
(Load)
Neutral 2 (White)
Neutral 1 (White)
Line 1 (120VAC)
Line 2 (277VAC)
Green
Ground
LOAD
White
Neutral
Load
Line
OR
120V Mark X™
Type Dimmer
Green
Ground
277V Hi-lume®
BALLAST
Orange
Black
OUTPUT
INPUT
)
Neutral
Load
Line
NEUTRAL
NEUTRAL
LO
AD
HO
T
SWITCH
HO
T
CONTR
OL
Wiring Diagram 3A
277 Dual Feed Wiring Application w/Mark X™ Ballast
Wiring Diagram 3B
277V Dual Feed Wiring Application w/Hi-lume
®
Ballast
CFM26W/GX24Q
CFM32W/GX24Q
CFM42W/GX24Q
CFQ26W/G24Q
F25T8
F25T8
F25T8
F32T8
F32T8
F32T8
FT40W/2G11
FT40W/2G11
VEZ-1T32
VEZ-1T32
VEZ-1T42
VEZ-2Q26
VEZ-132
VEZ-2S32
VEZ-3S32
VEZ-132
VEZ-2S32
VEZ-3S32
VEZ-1TTS40
VEZ-2TTS40
Advance
Mark X™
Part No.
Lamps
Max. # Ballasts
98
77
60
52
98
49
34
83
42
29
72
36
Single Gang
CFM26W/GX24Q
CFM32W/GX24Q
CFM42W/GX24Q
CFQ26W/G24Q
F25T8
F25T8
F25T8
F32T8
F32T8
F32T8
FT40W/2G11
FT40W/2G11
REZ-1T32
REZ-1T32
REZ-1T42
REZ-2Q26
REZ-132
REZ-2S32
REZ-3S32
REZ-132
REZ-2S32
REZ-3S32
REZ-1TTS40
REZ-2TTS40
Advance
Mark X™
Part No.
Lamps
Max. # Ballasts
62
50
39
33
62
32
22
53
27
18
47
24
Single Gang
Single Feed Wiring:
Line Hot can be controlled by one circuit breaker as long as
the total load does not exceed the rating of the circuit breakers.
Single Feed Wiring:
Line Hot can be controlled by one circuit breaker as long as the total load
does not exceed the rating of the circuit breakers.
Dual Feed Wiring:
The Input control circuit and the Output load circuit can be supplied by
two circuit breakers on a single phase or by two separate phases.
Dual Feed Wiring:
The Input control circuit and the Output load circuit can be supplied by
two circuit breakers on a single phase or by two separate phases.
Dual Feed Wiring:
The Input control circuit and the Output load circuit can be supplied by
two circuit breakers on a single phase or by two separate phases.
Dual Feed Wiring:
The Input control circuit and the Output load circuit can be supplied by
two circuit breakers on a single phase or by two separate phases.
Wiring Diagram 4: Dual Feed Wiring Application w/Controller
and Two Power Extenders (277V depicted)
Power
Extender
D3206/08
Controller/Dimmer
Hot (Black)
Hot (Black)
(Load)
(Load)
Neutral (White)
Neutral (White)
Neutral (White)
Line (120VAC)
Line 1 (277VAC)
Hot (Black)
Line 2 (277VAC)
Green
Ground
LOAD 2
277V MARK X™
DIMMABLE
BALLAST
Neutral
Load
Line
NEUTRAL
NEUTRAL
LO
AD
HO
T
SWITCH
HO
T
CONTR
OL
Power
Extender
NEUTRAL
NEUTRAL
LO
AD
HO
T
SWITCH
HO
T
CONTR
OL
LOAD 1
277V MARK X™
DIMMABLE
BALLAST
Dual Feed Wiring:
The Input control circuit and the Output load circuit can be supplied by
two circuit breakers on a single phase or by two separate phases.
NOTE:
Up to 4 Power Extenders can be connected together.