Leviton JCC JC50302 Installation Instructions Download Page 2

Month

Test Type

First Year

Second Year

Third Year

Fourth Year

Fifth Year

Sign 

Date

Sign

Date

Sign 

Date

Sign

Date

Sign 

Date

January

Functional

February

Functional

March

Functional

April

Functional

May

Functional

June

Functional

July

Functional

August

Functional

September

Functional

October

Functional

November

Functional

    December

3 hour

Installation Engineers:  ....................................................

Luminaire Type:  ...............................................................
Location:  ..........................................................................

 

Tel: ............................................................

Batch Number: ..........................................

Installation Date: ......................................

Emergency Test Record

General Information

These instructions contain important information regarding safety. They should be read carefully and retained at the installation for future reference.The 

company will not accept any responsibility for any injury, damage or loss that may arise as a result of incorrect installation, operation or maintenance due to 

the non-adherance to these instructions. Our products are designed to comply with the requirements of UK law and the relevant industry national and  

international standards and should not be modified in any way. All emergency lighting systems should comply with the recommendations of BS5266-1: Code 

of Practice for the Emergency Lighting of Premises and be installed by competent engineers in accordance with the relevant wiring regulations. Before  

installing any type of Emergency Lighting always seek the advice and approval of the local Fire Prevention Officer (or equivalent authority).

Maintenance

Failed or faulty light sources connected to this equipment should be replaced immediately. These units are designed especially for a long and trouble free life 

and, under normal conditions, will require no routine maintenance or service beyond the inspection and test regime of BS5266-1.

Both mains supply and battery protection fusing is incorporated internally. Should access to these or any other part of the circuitry be required this must be 

undertaken only by suitably qualified personel. Special care must be taken when removing the cover to circuitry and battery. Only replacement components 

authorised by the company must be used. Disposal of replaced components should be in accordance with the component manufacturers instructions.

Routine Inspection and Test

All tests must be undertaken at times of least risk and in accordance with EN 50172:2004 as indicated below:

Daily:

 Indicators of central power supply shall be visually inspected for  correct operation.

         

Monthly:

 (in addition to the daily check) 

If automatic testing devices are used, the results of the short duration tests shall be recorded.

Test shall be carried out as follows:

a) Switch on in the Emergency mode each luminaire and each internally illuminated exit sign from its battery by simulation of a failure of supply to the  

normal lighting for a period sufficient to ensure that each lamp is illuminated.

NOTE: The period of simulation failure should be sufficient for the purpose of this clause whilst minimising damage to the system components e.g lamps 

During this period, all luminaires and signs shall be checked to ensure that they are present, clean and functioning correctly. At the end of this test period, 

the supply to the normal lighting should be restored and any indicator lamp or device should be checked to ensure  that is showing that the normal supply 

has been restored.

Annually:

If automatic testing devices are used, the results of the short duration tests shall be recorded. For all other systems the monthly inspection shall be carried 

out and the following additional tests made:

a) each luminaire and internally illuminated sign shall be tested  Monthly as above but for its full duration in accordance with the manufacturer’s information;

b) the supply of the normal light shall be restored and any indicator lamp or device checked to ensure that it shows the normal supply has been restored. 

The charging arrangements should be checked for proper functioning;

c) the date of the test and its results shall be recorded in the system logbook.

A copy of this report must accompany any fitting returned to the manufacturer for any reason.

Reviews: