Installation instructions for JC50302 Emergency Exit Blade
Emergency Range
company
a
Important warranty information
This product is supported by a 2-year standard warranty which will extend to 3 years if registered within the first year of purchase.
(2 year on batteries). Please register at jcc.co.uk/warranty - Terms and conditions apply.
The installer will be asked to provide the following information, which is detailed on a label attached to the luminaire’s chassis:
Product Code/Date Code.
JCC Lighting Products Ltd. Innovation Centre, Beeding Close, Southern Cross Trading Estate, Bognor Regis, West Sussex, PO22 9TS, United Kingdom
Technical Support: +44(0)1243 838986 Customer Services: +44(0)1243 838999
BS EN ISO9001 - 2015 - Registered Firm Certificate No. GB 1552
V7_Apr_2021_GL
Warnings & Cautions
•
To avoid electric shock, serious injury or property damage,
isolate power before installing, removing or servicing the product.
•
It is recommended that luminaires are installed by a qualified
electrician to ensure the installation complies with the local current
wiring regulations.
•
It may be necessary to upgrade your MCBs to allow for increased
inrush current.
•
This product is designed for connection to a 220-240V~ 50/60Hz supply.
•
It is recommended that the ambient room temperature should not
exceed 30°C.
•
Read instructions and check that you have all of the tools and
accessories required to complete the installation correctly. Isolate power
supply before starting installation.
•
Do not carry out insulation tests with the product connected to
the circuit.
•
Any broken or damaged parts should be replaced as soon as possible.
JCC will not accept responsibility for claims arising from sub-standard
installations; which will void the warranty.
•
This luminaire is for indoor use only.
•
All testing should be carried out in accordance to
EN 50172:2004.
INSTALLATION
ENGLISH
RoHS
Compliant
IP20
jcc
.co.uk
Profile & Dimensions
All dimensions in millimetres
Non-replaceable light source
LED
LED
220-240V~ 50/60Hz - Class II
1. To remove the back cover press the tabs at each end to release.
2. Cable entry is available through the rear only.
3. Use the back plate as a template to mark for holes to securing the
fitting, ensuring suitable fixings are used for the intended location.
4. For wall or ceiling mounting ensure that the cable entry is on the left
and that the fitting is mounted with the test button and indicator light
facing forward to the right hand side.
5.
For wall mouting, this will ensure that the fitting lays 90° to the wall
surface and the blade in a vertical position.
6. Connect the mains input supply as indicated above as per the required
operation.
7. Connect the emergency battery leads to the circuit board (top right
hand corner - next to the batteries).
8. For non-maintained operation, remove jumper as instructed on circuit
board.
9. Refit the body to the base.
10.
Using the 4 press clips supplied, fit the two corresponding legends to
the blade to suit the application.
11. Switch on mains supply and test for operation (allow 24hrs for
batteries to charge).
12.
Familiarise yourself with the enclosed emergency fittings test record
sheet and ensure it is completed as required and left with the end user.
1. With mains supply on and green indicator light on, press the Test
button to check function.
2.
Green indicator light will go off and the fitting will operate in
emergency mode.
3.
Release the button and the inidcator light will come on and the fitting
will then return to previous operation.
Light source:
Total circuit Wattage:
Total circuit Wattage:
Luminous flux:
Luminous flux:
Efficacy:
Efficacy:
Ra:
Integral LED
2.8W
(AC)
2.88W(DC)
46 lumens(AC)
46 lumens(DC)
16 LpcW(AC)
16 LpcW(DC)
78
Installation
Function test
Neutral: Blue
U/sw Live: Brown
Maintained(3M)
+ Light on 24/7
Non-Maintained
(3NM)
+ Light off 24/7
+ Emergency
For non-maintained operation
remove jumper as instructed on
circuit board.
233mm
36mm
309mm
Available legends to order:
JC50308 - 1 x left & 1 x right running man
JC50310 - 2 x Down running man
JC50311 - 2 x Up running man
Legends not supplied