Hook Detail
Left Cover
Enclosure
INSTALL COVERS AND DOORS
NOTE: The Cover and Door assembly consists of four components; lower vent plate, left cover, right cover,
and the door.
NOTE: The covers and lower vent plate must be in place when any circuit in the cabinet is energized.
1. To install the left and right covers, start a mounting screw in the
second from the bottom
screw hole on the
cabinet flange. Do not completely tighten screw but leave enough space for the thickness of the cover. Locate
the upper mounting hook on the cover and the corresponding tab on the enclosure. Locate the keyhole slot at
the
second from the bottom
location. Align both the hook and the keyhole slot with their mating features of
the cabinet and slide in place.
See Hook Detail.
2. Install all mounting screws provided to permanently fasten the covers in place.
3. Install the lower ventilation panel by sliding mating tabs of the left and right covers through the slots provided
in the ventilation plate. Lower the ventilation plate into place and fasten with mounting screws.
4. Install the door by sliding the halves of the hinges together. Hang the door on one hinge pin at a time, the pins
are different lengths to facilitate easy assembly.
LIMITED 10 YEAR WARRANTY AND EXCLUSIONS
Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship under normal and proper use for ten years from the purchase date. Leviton’s only obligation is to correct such defects by repair or
replacement, at its option, if within such ten year period the product is returned prepaid, with proof of purchase date, and a description of the problem to
Leviton Mfg. Co., Inc. 201 North Service Road, Melville, N.Y. 11747, U.S.A. This warranty excludes and there is disclaimed liability for labor for removal of this product
or reinstallation. This warranty is void if this product is installed improperly or in an improper environment, overloaded, misused, opened, abused, or altered in any manner, or is not used under normal operating conditions or not in accordance with any labels or instructions.
There are no other or implied warranties of
any kind, including merchantability and fitness for a particular purpose, but if any implied warranty is required by the applicable jurisdiction, the duration of any such implied warranty, including merchantability and fitness for a particular purpose, is limited to ten years. Leviton is not liable for incidental, indirect,
special, or consequential damages, including without limitation, damage to, or loss of use of, any equipment, lost sales or profits or delay or failure to perform this warranty obligation. The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.
For Technical Assistance Call: 1-800-959-6004 (U.S.A. Only)
www.leviton.com
COMMAND MODULE DETAIL
Power Supply
Ground power
supply here
MPU
Feed wires
through hole
Mounting Tabs
DIP Switch
Low Voltage
Input Card
16 Inputs shown
LumCan Ports
4 LumCan Ports
DIP Switch
Hinge
32 Relay Cabinet
48 Relay Cabinet
16 Relay Cabinet
Lower
Vent
Plate
Keyhole
Slot &
Temporary
Mounting
Screw
Right
Cover
Left
Cover
Lock
Door
DIP SWITCH SETTINGS
Set the ID Address of the Command Module and Low Voltage
Input Card - Examples shown below
ID 1
ID 2
ID 3
ID 4
ID 5
ID 6
ID 38 ID 86
1
2
4
8
16
32
64
128
O N
1 2 3 4 5 6 7 8
O N
1 2 3 4 5 6 7 8
O N
1 2 3 4 5 6 7 8
O N
1 2 3 4 5 6 7 8
O N
1 2 3 4 5 6 7 8
O N
1 2 3 4 5 6 7 8
O N
1 2 3 4 5 6 7 8
O N
1 2 3 4 5 6 7 8
ID Address Value = Sum of Switch Values
ID 86 = 2+4+16+64
Switch
Values
PK-93838-10-00-0A-X2
© 2010 Leviton Mfg. Co., Inc.
64"
48"
31-1/2"