The total lamp wattage connected to each channel must not exceed the rating of each channel (see
SPECIFICATIONS). For inductive loads, the total lamp volt-amperes plus the volt-amperes of any ballast or
transformer must not exceed the rating of each channel.

NOTE: Some inductive type loads, such as transformers, ballasts, and motors with poor factor power
may cause the dimmer to output DC type current. This may cause the load to draw excessive current and
overheat, causing damage to the transformer, ballast or motor. For this reason, it is necessary to insure
any inductive loads are fused individually for their respective normal operating current.

PERMANENT CONNECTION

The DDS 6000 is available as an optional DDS 6000 Plus - 20 terminal version. This version must be installed
by qualified personnel.

AC Input

Conduit containing line conductors enters pack through one of the knockouts in the top end. The two 20A,
120V, 60Hz, 2 wire line circuits, A and B, are terminated to their respective terminals labeled Line and Line N.
The terminals accept wire sizes 22-8 AWG CU and have a torque rating of 8 in-lbs. Line equipment grounding
conductor, if a wire, terminates to the lug labeled GND. The ground lug accepts wire size 14-6 AWG CU and
has a torque rating of 35 in-lbs. (14-10 AWG), 40 in-lbs. (8 AWG), and 45 in-lbs. (6 AWG).

AC Output

Conduit containing load conductors enters pack through one of the knockouts in the top end. The four 1200 W
max., 120V, wire load circuits, 1 through 4, are terminated to their respective terminals labeled Load and Load
N. Circuits 1 and 2 are supplied from input A, and circuits 3 and 4 from input B. The control power supply is also
supplied by input A. Terminal rating are the same as indicated above for line terminals.

LED INDICATORS

The front panel indicator LEDs indicate the status of the relay.

RED — Indicates the firing card is receiving DC power.

GREEN — Steady indicates a multiplex control signal is being received.

YELLOW — Indicates a respective dimmer channel is active and the LED indicates relative intensity.

CHANNEL FUSES

Each channel is protected by a fuse to help prevent overload and damage to the power control devices used
in the dimmer. Be sure to replace the fuse with the same type of rating. Replacement with the wrong fuse is
dangerous and will void your warranty.

NOTE: Lamps may sometimes cause a temporary “short-circuit” when the filament burns out and
cause the fuse to blow. This is normal and protects the internal dimmer circuitry from damage.

CHANNEL

ONE

CHANNEL

FOUR

CHANNEL

THREE

CHANNEL

TWO

DDS 6000

DIGITAL DIMMING SYSTEM

1200 WATTS PER CHANNEL

INDOOR USE ONLY
AC LIGHTING ONLY

CONTROL WIRING CLASS 2

LISTED

IND. CONT. EQ.

2J80

UL

C

US

LEVITON MFG. CO., INC.       TUALATIN, OR

INPUT RATING

120V, 60HZ, 1800W

120V, 60HZ, 2400W

2 @ 120V, 60HZ,

1800W

2 @ 120V, 60HZ,

2400W

OUTPUT RATING

120V, 60HZ, 1200W PER CHANNEL

NOT TO EXCEED 1800W TOTAL

120V, 60HZ, 1200W PER CHANNEL

NOT TO EXCEED 2400W TOTAL

120V, 60HZ, 1200W PER CHANNEL

NOT TO EXCEED 1800W PER INPUT TOTAL

120V, 60HZ, 1200W PER CHANNEL

NOT TO EXCEED 2400W PER INPUT TOTAL

MODEL

DDS 6000 - 15

DDS 6000 - 20

DDS 6000
PLUS - 15

DDS 6000
PLUS - 20

Page 5

MICROPLEX MULTIPLEX CONTROL WIRING

Microplex is the control protocol used on  most Leviton-NSI lighting consoles. This
system uses a single three conductor cable to transmit up to 128 channels of
dimmer control. For short distances (50 feet or less) a standard microphone cable
may be used to carry both the control signal and the DC power source for Leviton-
NSI control consoles. Longer distances may be accommodated with 18 gauge or
better cable to reduce voltage losses of the power supply.

Connect the Microplex control cable to either of the three pin XLR jacks. Since
both jacks are wired in parallel, another control cable may be connected between
the remaining jack and another dimmer pack. Many dimmer packs may be “daisy
chained” together in this manner.

Be sure to set the Channel Address DIP switch as required (see ADDRESSING).

ANALOG 0-10 VDC CONTROL WIRING

Each of the four channels of the DDS 6000 may be operated by an analog
0-10 VDC control voltage. This type of control will provide 0% intensity at 0
volts and 100% intensity at 10 volts. Any or all of the DDS 6000 dimmer
channels may be operated in this manner simultaneously with any multiplex
control input. Each dimmer will respond to the greater of any control inputs.

The analog control input uses a standard 5 pin DIN plug which is available
from most electronics supply houses. Connect each if the positive channel
control wires to the desired dimmer channel input pins of the plug. Connect
the common (ground) control wire to the pin indicated on the diagram. Consult the documentation of the analog
control console or device you are using for the proper connections. The control input impedance is 4.7K ohms.

DMX512 MULTIPLEX CONTROL WIRING

DMX512 is the United States Institute of Theater Technology
(USITT) standard for the digital control of dimmers. Leviton-
NSI DDS dimmer products can be converted from Microplex
to DMX512 digital multiplex with a simple kit available from
your dealer.

DMX512 is the preferred type of control wiring when many
dimmer channels are used, because of the high update rate
and the resistance to interference. It is recommended in
locations subject to electrical noise. DMX512 only requires 3
wires to transmit lighting levels for as many as 512 relay or
dimmer channels. Most of the Leviton-NSI lighting control consoles can optionally use this interface.

Connect the DMX512 cable from the control console to the male input connector. Another cable may be
connected from the female connector to the male connector of another pack. Many dimmer packs may be
“daisy chained” or connected together in this manner.

Be sure to set the Channel Address DIP switch as required (see ADDRESSING).

AUTO LAMP TEST

Whenever DIP switch #8 is in the OFF (down) position and there is no multiplex signal detected, all channel
outputs will come to full intensity. The automatic sequencing feature must be disabled for this Auto Lamp test to
operate.

1

2

3

Common

0-10V Input

4

5

Channel 3

Channel 2

Channel 4

Channel 1

MULTIPLEX LOOP THRU

LEVITON MFG. CO., INC.

TUALATIN, OREGON

MPX ADDRESS

12345678

FUSES

1

2

3

4

FUSES

USE ONLY

12A, 250V

NON-TIME-DELAY

FUSES

USE ONLY

12A, 250V

NON-TIME-DELAY

FUSES

0-10VDC INPUT

PWR MPX

1

2

3

4

1

2

3

4

5

N / C

N / C

Common

DMX Data -

DMX Data +

Female DMX512

XLR Pin Configuration

MPX Data

2

1

3

+15 VDC

Common

Female Microplex

XRL Pin Configuration

Summary of Contents for DDS 6000+

Page 1: ...Page 1 PK 93381 10 00 0B DDS 6000 6000 SATELLITE DIMMER PACKS USER GUIDE Software Revision 1 0 and above Document Revised 8 30 02 Copyright 2002 Leviton Manufacturing Co Inc ...

Page 2: ...AC Input 4 AC Output 4 LED INDICATORS 4 CHANNEL FUSES 4 MICROPLEX MULTIPLEX CONTROL WIRING 5 ANALOG 0 10 VDC CONTROL WIRING 5 DMX512 MULTIPLEX CONTROL WIRING 5 AUTO LAMP TEST 5 INTERNAL CONFIGURATION DIP SWITCH SELECTION 6 Softstart 6 NON DIM Channels Relay Mode 6 AUTO SEQUENCING MODE 6 INSTALLATION AND OPERATION TIPS 6 ADDRESSING 7 ...

Page 3: ...with the NEMA 5 20 plug will support 2400 Watts The DDS 6000 Plus includes two cords one per each two channels which doubles the maximum capacity The power cord s must be connected to a power source capable of supplying the total power drawn by the lights See SPECIFICATIONS for details on maximum power capability AC OUTPUT RECEPTACLES The DDS 6000 has two AC receptacles for each channel These rece...

Page 4: ...rcuits 1 through 4 are terminated to their respective terminals labeled Load and Load N Circuits 1 and 2 are supplied from input A and circuits 3 and 4 from input B The control power supply is also supplied by input A Terminal rating are the same as indicated above for line terminals LED INDICATORS The front panel indicator LEDs indicate the status of the relay RED Indicates the firing card is rec...

Page 5: ...control console or device you are using for the proper connections The control input impedance is 4 7K ohms DMX512 MULTIPLEX CONTROL WIRING DMX512 is the United States Institute of Theater Technology USITT standard for the digital control of dimmers Leviton NSI DDS dimmer products can be converted from Microplex to DMX512 digital multiplex with a simple kit available from your dealer DMX512 is the...

Page 6: ...osition on the firing cards as indicated below Moving the switch to ON will restore dimming operation AUTO SEQUENCING MODE The DDS 6000 dimmers can be configured to perform stand alone Automatic Sequencing in place of Auto Lamp Test This is useful for lighting displays and show windows The four channels will automatically fade from one to another in a preprogrammed pattern and time selected by the...

Page 7: ...11111 1234567 0000000 1100000 0110000 1001000 0011000 1111000 0100100 1010100 0001100 1101100 0111100 1000010 0010010 1110010 0101010 1011010 0000110 1100110 0110110 1001110 0011110 1111110 0100001 1010001 0001001 1101001 0111001 1000101 0010101 1110101 0101101 1011101 0000011 1100011 0110011 1001011 0011011 1111011 0100111 1010111 0001111 1101111 0111111 CONTROL 5 8 17 20 29 32 41 44 53 56 65 68 ...

Page 8: ... for labor for removal of this product or reinstallation This warranty is void if this product is installed improperly or in an improper environment overloaded misused opened abused or altered in any manner or is not used under normal operating conditions or not in accordance with any labels or instructions There are no other or implied warranties of any kind including merchantability and fitness ...