Page 19
Installation & Operation Guide
Installation & Operation Guide
Page 4
MOUNTING
The 2408 CD Dimmer pack or 2408 CR Relay pack must be mounted
securely in a dry location to the surface of a wall or other vertical flat
surface in a manner which is capable of supporting it’s weight. Nine
“key-hole” type mounting holes for 1/4” lag screws are provided in
the back wall of the unit for this purpose (figure 1).
Since the 2408 CD/CR depends upon convection cooling, room
airflow must not be prevented by walls or other obstructions.
Adequate side and top clearances from adjacent walls and
equipment are necessary:
If several units are to be installed in a small-enclosed room,
adequate ventilation must be provided to prevent the room
temperature from exceeding 100 degrees Fahrenheit.
Clear working space and access to the 2408 CD/CR must be
provided in accordance with electrical codes.
INSTALLATION
Minimum distance from top to ceiling:
Minimum distance from top to other equipment:
Minimum distance from side adjacent to wall:
Minimum distance from side to other equipment:
36”
12”
12”
6”
Figure 1
MOUNTING
INSTALLATION
5.750
11.500
1.250
17.500
14.000
5.000
20.250
8.875
17
.750
1.750
1/4” Mounting Screw Max.
(9 PLCS)
Summary of Contents for 2408CD
Page 2: ......