RFM-Setup tipps

 

Leuze 

electronic

 

Page 2 of 3 

Leuze 

electronic

 

 
RFM 12/ RFM 32/ RFM 62 on PROFIBUS via MA 42 DP-k 

 

After mounting of the RFM and the MA, turn the address switch of each MA 42 
to the dedicated address. By the integration of the GSD-file into the PROFIBUS 
master, all configuration data of the MA 42 is usable for the PLC. The 
configuration of the  RFM is done very easy via service interface of the MA42 
and the RF-config tool. To do so please set all 3 DIP–switches to „Service“or 
“RS 232“. When the configuration is finished set back the DIP-switches 
to„Betrieb“ or „PROFIBUS“(operation).  
The complete configuration telegram could be send directly from the PLC to 
the RFM (like a Command telegram). The structure and the description of the 
parameters are in the “telegram and command structure” file. 
If communicating to the RFM device via PROFIBUS please note that each 
character is handled as ASCII-character and must be transfered into 
hexadecimal . With commands or telegrams longer than 6 Byte (including pre- 
and postfix), each part of the telegram has to be stored in the memory of the 
MA 42 (look for correct sequence). If the telegram/ command is complete in the 
memory of the  MA 42, transfer the whole content with the bit „SFB“ to the 
RFM. After the transfer, the memory of MA 42 has to be deleted.  
For more details concerning the MA 42 please see the technical manual  
MA 40/ MA 41/MA 42 DP-k  
 
 
RFM 12/ RFM 32/ RFM 62 on PROFIBUS via MA 204i 

 

After mounting of the RFM and the MA, turn the address switch of each MA 
204i to the dedicated address. By the integration of the GSD-file into the 
PROFIBUS master, all configuration data of the MA 204i is usable for the PLC. 
The configuration of the RFM is done very easy via service interface of the 
MA204i and the RF-config tool. To do so please set all DIP–switches to 
„„Service“and“DEV “.When the configuration is finished set back the DIP-
switches to„RUN“(operation). 
The complete configuration telegram could be send directly from the PLC to 
the RFM (like a Command telegram). The structure and the description of the 
parameters are in the “telegram and command structure” file. 
 If communicating to the RFM device via PROFIBUS please note that each 
character is handled as ASCII-character and must be transfered into 
hexadecimal . With very long commands or telegrams, each part of the 
telegram has to be stored in the memory of the MA 204i in the collecting mode 
(look for correct sequence). If the telegram/ command is complete in the 
memory of the  MA 204i, transfer the whole content with the bit „SFB“ to the 
RFM. For more details concerning the MA 204i please see the technical manual  
 
 
 
 
 
 
 
 
 