Diagnostics and troubleshooting
12.1
General causes of errors
Error
Possible error cause
Measures
Control receives no
measurement data
Ethernet connection
interrupted
Check connection with LESsoft.
See "Commissioning" on page 63.
Control not connected to
sensor
Use "To sensor" command.
Object contours not
detected
Occlusion
Soiling of the
optics covers
Clean optics covers,
see "Cleaning" on page 127.
Ambient light
Prevent ambient light, shield sensor, see "Selecting a
mounting location" on page 39.
Limit detection range with LPSsoft, see "Field of
View" on page 76.
Reflections
Avoid reflections.
Limit detection range with LPSsoft, see "Field of
View" on page 76.
Unsuitable exposure
setting
Adapt exposure duration to the reflective properties of
the objects to be detected. See "Light Exposure" on
page 76.
Object not in
measurement range
Visual assessment with LESsoft,
reduce working distance/position of the sensor to the
object. See "Standard tab - Task Parameters panel"
on page 75.
Detection range selected
too small
Configure detection range with LESsoft.
See "Field of View" on page 76.
Wrong inspection task
selected
Change inspection task with LESsoft or use Ethernet
command "Set Actual Inspection Task". See "Set
Actual Inspection Task" on page 103.
Sensor does not respond to
commands
Sensor in measure/menu
mode
Exit menu view on OLED display.
Connect sensor to control. Switch sensor to command
mode if necessary.
Sensor not connected
Check settings of the Ethernet interface. Connect
sensor to control.
Sensor not activated
Activate sensor via PIN 2 on X1.
Switch off activation input. See "Activation" on
page 76.
Table 12.1:
General causes of errors