PROFINET
Leuze electronic
DCR 248i
66
Tab. 10.10:
Input data structure module 23
Input data
Address
Data type
Value range
Default
Unit
Explanation
Activation
status
0.0
Bit
0: Deactivated
1: Activated
0
---
Displays the current
activation status.
Reserved
0.1
Bit
0
---
Free
User data re-
sult or Cmd
interpreter re-
sponse
0.2
Bit
0: User data
1: Cmd inter-
preter response
0
---
Distinction between re-
sult from the Formatter
and answer from the
Cmd interpreter.
Makes the distinction
easy for the user.
Further re-
sults in the
buffer
0.3
Bit
0: No
1: Yes
0
---
Signal indicates
whether further results
are in the buffer.
Buffer over-
flow
0.4
Bit
0: No
1: Yes
0
---
Signal indicates that
result buffer is occu-
pied and the device re-
jects data.
New result
0.5
Bit
0->1: New result
1->0: New result
0
---
The toggle bit indicates
whether a new result is
present.
Reserved
0.6
Bit
0
---
Free
Waiting for
acknowledg-
ment
0.7
Bit
0: Base state
1: Control waiting
for acknowledge-
ment from the
master
0
---
This signal represents
the internal state of the
control.
Result data
length
1
UN-
SIGNED 16
0-65535
0
---
Data length of the ac-
tual result information.
Data
3..34
32x
UN-
SIGNED8
0-FFh
0
---
Result information with
a length of consistently
32 bytes.
Input data length: 3 bytes consis 32 bytes of result information
10.4.8 Module 24 – Result data 4
PROFINET-IO module identifier
• Module ID: 1024
• Submodule ID: 1
NOTICE
Ä
Modules 21 … 28 can only be used one at a time, not simultaneously.
Ä
If the result information (result plus additional information, such as the code quality) does not
fit in the selected module width, the information is shortened.
The transmitted result data length is an indication of shortening of the result information.
Description
The module defines the transfer of the result data. The result data comes from the Formatter currently se-
lected. The Formatter can be selected and configured in the webConfig tool (see chapter 9.3 "webConfig
tool").